Plan Review Notes
Plan Review Notes For Permit 14100545
Permit Number 14100545
Review Stop E
Sequence Number 1
Notes
Date Text
2014-10-20 13:55:171. SHOW COMPLETE SERVICE RISER DIAGRAM. SUBMITTED PLAN
 SHOWS DOUBLE LUGGED METER CAN.
 2. N.E.C. 225.31,225.32,225.36. DISCONNECTING MEANS TO
 MEET CRITERIA OF CODE SECTION NOTED FOR SEPARATE
 BUILDING.
 3. N.E.C. 250.32 (D). GROUNDING OF SEPARATE BUILDING OR
 STRUCTURE ON SAME PREMISES.
 4. N.E.C. 210.52 (B) (1). DINING ROOM RECEPTACLE TO BE
 ON SMALL APPLIANCE CIRCUIT. NOT GENERAL LIGHTING.
 5. N.E.C. 422.11 (E). OCPD FOR 5000 WATT WATER HEATER.
 ON PANEL SCHEDULE.
 6. MECHANICAL PLAN SHOWS 5 KW AHU. CHECK OCPD ON PANEL
 SCHEDULE.