2014-10-20 08:53:59 | 1) CITY RECORDS DO NOT SHOW ANY PERMITS FOR THE | | INSTALLATION OF COOKING EQUIPMENT, THE REQUIRED HOOD | | EXHAUST FOR THE EQUIPMENT, OR LP TANKS. COMMERCIAL | | COOKING APPLIANCES SHALL BE VENTED IN ACCORDANCE WITH | | THE FGC SEC.623.6, 505.1. THE GAS APPLIANCES SHALL BE | | INTERLOCKED WITH THE EXHAUST HOOD. THIS GAS PERMIT | | CANNOT BE ISSUED UNTIL A HOOD AND SUPPRESSION SYSYTEM | | IS SUBMITTED FOR REVIEW AND APPROVAL. | | 2) THE GAS APPLIANCES SHALL BE LISTED AND LABELED PER | | THE FGC SEC. 301.3. MANUF. SPEC SHEETS FOR THE GAS | | APPLIANCES SHALL BE SUBMITTED FOR REVIEW. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | |
|