Plan Review Notes For Permit 14100487 |
Permit Number |
14100487 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-11-03 12:07:22 | PLAN DENIED | | | | 1) PROVIDE EQUIPMENT SCHEDULE ON PLANS | | PER SECTION 107 FBC 2010 | | 2) PROVIDE CFM ON ALL SUPPLY DROPS. | | PER SECTION107 FBC 2010 | | 3) NEED ARCHITECT STAMP AND SIGNATURE | | ON THE PLANS. | | 4) REFER TO SECTION 601.4 BALANCED | | RETURN AIR 2010 FBC (M) | | 5) ENERGY CALCULATIONS AND PLANS | | DO NOT MATCH | | 6) SHOW LOCATION OF THE CONDENSER'S | | ON THE PLANS SECTION 107 | | 7) SHOW BATH EXHAUST ON THE PLAN | | AND EXHAUST DISCHARGE. PER SECTION | | 501.2 FBC (M) 2010 | | 8) SHOW LOCATION OF THE CONDENSATE | | FOR THE A/C UNITS PER SECTION 307 FBC (M) | | 9) REFER TO SECTION 307.2.3.1 WATER LEVEL | | MONITORING DEVICE 2010 FBC (M) | | 10) REFER TO SECTION 306.3.2 AIR HANDLING UNITS | | 2010 FBC (M) | | 11) REFER TO SECTION 306.3 APPLIANCES IN ATTIC | | 2010 FBC (M) | | 12) REMOVE THE NOTE ON THE PLAN THAT STATES | | FOR PRELIMINARY PERMIT DO NOT USE FOR CONSTRUCTION. | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 | | | | |
|