Plan Review Notes
Plan Review Notes For Permit 14100487
Permit Number 14100487
Review Stop E
Sequence Number 1
Notes
Date Text
2014-10-16 16:17:5310/16/2014
 PROJECT: URGENT CARE
 PERMIT#: 14100487
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1
 INNCLUDING SIGNS SHALL HAVE AUTOMATIC CONTROLS TO TURN
 OFF AT DAYLIGHT OR WHEN NOT REQUIRED. CONTROLS SHALL BE
 PHOTOSENSOR & TIME CLOCK OR ASTRONOMICAL TIME SWITCH.
 ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING
 PROGRAMING DURING A LOSS OF POWER FOR A MINIMUM OF 10
 HOURS. FBC-E 505.2.4
  
 2) 517.13 GROUNDING OF RECEPTACLES AND FIXED ELECTRICAL
 EQUIPMENT IN PATIENT CARE AREAS. WIRING IN PATIENT CARE
 AREAS SHALL COMPLY WITH 517.13(A) AND (B).
 (A) WIRING METHODS. ALL BRANCH CIRCUITS SERVING PATIENT
 CARE AREAS SHALL BE PROVIDED WITH AN EFFECTIVE
 GROUND-FAULT CURRENT PATH BY INSTALLATION IN A METAL
 RACEWAY SYSTEM, OR A CABLE HAVING A METALLIC ARMOR OR
 SHEATH ASSEMBLY. THE METAL RACEWAY SYSTEM, OR METALLIC
 CABLE ARMOR, OR SHEATH ASSEMBLY SHALL ITSELF QUALIFY AS
 AN EQUIPMENT GROUNDING CONDUCTOR IN ACCORDANCE WITH
 250.118.
 (B) INSULATED EQUIPMENT GROUNDING CONDUCTOR. THE
 GROUNDING TERMINALS OF ALL RECEPTACLES AND ALL
 NON?CURRENT CARRYING CONDUCTIVE SURFACES OF FIXED
 ELECTRICAL EQUIPMENT LIKELY TO BECOME ENERGIZED THAT
 ARE SUBJECT TO PERSONAL CONTACT, OPERATING AT OVER 100
 VOLTS, SHALL BE CONNECTED TO AN INSULATED COPPER
 EQUIPMENT GROUNDING CONDUCTOR. THE EQUIPMENT GROUNDING
 CONDUCTOR SHALL BE SIZED IN ACCORDANCE WITH TABLE
 250.122 AND INSTALLED IN METAL RACEWAYS OR AS A PART OF
 LISTED CABLES HAVING A METALLIC ARMOR OR SHEATH
 ASSEMBLY WITH THE BRANCH-CIRCUIT CONDUCTORS SUPPLYING
 THESE RECEPTACLES OR FIXED EQUIPMENT.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  