| PROJECT: URGENT CARE |
| PERMIT#: 14100487 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| ELECTRICAL PLAN REVIEW |
| ACTION: PROVISO |
| |
| 1) ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 |
| INNCLUDING SIGNS SHALL HAVE AUTOMATIC CONTROLS TO TURN |
| OFF AT DAYLIGHT OR WHEN NOT REQUIRED. CONTROLS SHALL BE |
| PHOTOSENSOR & TIME CLOCK OR ASTRONOMICAL TIME SWITCH. |
| ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING |
| PROGRAMING DURING A LOSS OF POWER FOR A MINIMUM OF 10 |
| HOURS. FBC-E 505.2.4 |
| |
| 2) 517.13 GROUNDING OF RECEPTACLES AND FIXED ELECTRICAL |
| EQUIPMENT IN PATIENT CARE AREAS. WIRING IN PATIENT CARE |
| AREAS SHALL COMPLY WITH 517.13(A) AND (B). |
| (A) WIRING METHODS. ALL BRANCH CIRCUITS SERVING PATIENT |
| CARE AREAS SHALL BE PROVIDED WITH AN EFFECTIVE |
| GROUND-FAULT CURRENT PATH BY INSTALLATION IN A METAL |
| RACEWAY SYSTEM, OR A CABLE HAVING A METALLIC ARMOR OR |
| SHEATH ASSEMBLY. THE METAL RACEWAY SYSTEM, OR METALLIC |
| CABLE ARMOR, OR SHEATH ASSEMBLY SHALL ITSELF QUALIFY AS |
| AN EQUIPMENT GROUNDING CONDUCTOR IN ACCORDANCE WITH |
| 250.118. |
| (B) INSULATED EQUIPMENT GROUNDING CONDUCTOR. THE |
| GROUNDING TERMINALS OF ALL RECEPTACLES AND ALL |
| NON?CURRENT CARRYING CONDUCTIVE SURFACES OF FIXED |
| ELECTRICAL EQUIPMENT LIKELY TO BECOME ENERGIZED THAT |
| ARE SUBJECT TO PERSONAL CONTACT, OPERATING AT OVER 100 |
| VOLTS, SHALL BE CONNECTED TO AN INSULATED COPPER |
| EQUIPMENT GROUNDING CONDUCTOR. THE EQUIPMENT GROUNDING |
| CONDUCTOR SHALL BE SIZED IN ACCORDANCE WITH TABLE |
| 250.122 AND INSTALLED IN METAL RACEWAYS OR AS A PART OF |
| LISTED CABLES HAVING A METALLIC ARMOR OR SHEATH |
| ASSEMBLY WITH THE BRANCH-CIRCUIT CONDUCTORS SUPPLYING |
| THESE RECEPTACLES OR FIXED EQUIPMENT. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |