2014-11-13 16:48:06BUILDING PLAN REVIEW
 PERMIT: 14100487
 ADD: 5818 S. DIXIE HWY.
 CONT: MACO CONSTRUCTION
 TEL: (561)379-3171
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. NOV. 13/ 2014
 ACTION: DENIED
  
 1) SITE PLAN:
 1A) PLEASE SEE THE 2010 FL ACCESS. CODE FOR AN
 ACCESSIBLE AISLE WIDTH. 2010 FL. ACCESS. CODE 502.3.1.
 ACCESS AISLES SERVING CAR AND VAN PARKING SPACES SHALL
 BE 60 INCHES (1525 MM) WIDE MINIMUM.
  
 1B) THE ACCESS AISLE IS ALSO TO BE DOUBLE STRIPED PER
 CITY MUNI. CODE 94-485. PLEASE SEE 2010 ACCESS.
 ADVISORY 502.3.3 MARKING. THE METHOD AND COLOR OF
 MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT MAY
 BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS.
 BECAUSE THESE REQUIREMENTS PERMIT THE VAN ACCESS AISLE
 TO BE AS WIDE AS A PARKING SPACE, IT IS IMPORTANT THAT
 THE AISLE BE CLEARLY MARKED.
  
 2) THE PLANS INDICATE THIS REMODEL IS TO BECOME A
 URGENT CARE FACILITY. NOTE IF IT IS CONSIDERED A
 REHABILITATION FACILITIES AND OUTPATIENT PHYSICAL
 THERAPY FACILITIES SEE ADVISORY:
 ADVISORY 208.2.2 REHABILITATION FACILITIES AND
 OUTPATIENT PHYSICAL THERAPY FACILITIES. CONDITIONS THAT
 AFFECT MOBILITY INCLUDE CONDITIONS REQUIRING THE USE OR
 ASSISTANCE OF A BRACE, CANE, CRUTCH, PROSTHETIC DEVICE,
 WHEELCHAIR, OR POWERED MOBILITY AID; ARTHRITIC,
 NEUROLOGICAL, OR ORTHOPEDIC CONDITIONS THAT SEVERELY
 LIMIT ONE?S ABILITY TO WALK; RESPIRATORY DISEASES AND
 OTHER CONDITIONS WHICH MAY REQUIRE THE USE OF PORTABLE
 OXYGEN; AND CARDIAC CONDITIONS THAT IMPOSE SIGNIFICANT
 FUNCTIONAL LIMITATIONS.
  
 IF THIS UNIT IS CONSIDERED A REHABILITATION FACILITIES
 AND OUTPATIENT PHYSICAL THERAPY FACILITIES, THEN
 PARKING COMPLIANCE WITH:
 FL ACCESS. CODE IS REQUIRED. 208.2.2 REHABILITATION
 FACILITIES AND OUTPATIENT PHYSICAL THERAPY FACILITIES.
 TWENTY PERCENT OF PATIENT AND VISITOR PARKING SPACES
 PROVIDED TO SERVE REHABILITATION FACILITIES
 SPECIALIZING IN TREATING CONDITIONS THAT AFFECT
 MOBILITY AND OUTPATIENT PHYSICAL THERAPY FACILITIES
 SHALL COMPLY WITH 502.
  
 3) MISSING SOILS REPORT. SHEET S-2 NOTE # 2 INDICATES
 THE SAFE MINIMUM BEARING VALUE OF THE SOIL IS 2500 PSF.
 NOTE # 1 INDICATES A SOILS ENGINEER IS TO PROVIDE A
 SOILS AND FOUNDATION INVESTIGATION REPORT BY AN
 APPROVED TESTING LABORATORY. 2010 FBC-B. 1803.5.2
 QUESTIONABLE SOIL.
  
 4) FLORIDA ENERGY GAUGE REPORT FORM 506-2010
 PERFORMANCE BASED COMPLIANCE.
  
 4A) THE ENERGY GAUGE REPORT INDICATES THE EXTERIOR WALL
 INSULATION IS TO BE A R-4.8 VALUE. SHEET A-3 DETAIL #
 10 SHOWS THE R4.8 INSULATION BUT THE DETAIL DOES NOT
 PROVIDE HOW HIGH THE EXTERIOR WALL INSULATION IS TO BE
 INSTALLED. ENERGY 506.3.2.
  
 4B) THE ENERGY GAUGE REPORT INDICATES THE EXTERIOR PAIR
 OF DOORS ARE ALUMINUM DOORS W/ (2) SIDE LITES, 1.25 IN.
 W/ POLYSTYRENE INSULATION. THES DOORS ARE OVER 50%
 GLAZED DOORS AND SHOULD BE TAKEN AS WINDOWS. THE WINDOW
 SIZES PROVIDED DO NOT CORRELATE WITH THE SIZES PROVIDED
 ON THE PLANS.
 THE REPORT LIST THE SHGC AS 0.50 THE SHADING
 COEFFICIENT HAS NOT BEEN DEMINTRATED, AND THE REPORT
 ALSO INDICATES THE WINDOWS ARE NOT SHADED, WHERE AS THE
 PLANS INDICATE THE USE OF BAHAMA SHUTTERS OVER THE
 WINDOWS AND A PORCH OVER THE FRONT ENTRY.
  
 4C) DISCREPANCY IN REPORT UNDER THE HEADING ROOFING
 PAGE 3, ZONE PR)ZO1 THE REPORT INDICATES THE ROOFING
 INSULATION TO BE 4 IN. ISO/ METAL ROOF DECK W/ BUILT UP
 ROOF 2 IN. OF GRAVEL. ROOF VALUE OF R 6.7. PAGE 7 NAME
 BUILT UP ROOF INDICATES BUILT UP ROOF GRAVEL/ 2IN. ISO/
 METAL DECK THE R VALUE OF 6.7 WITHOUT THE 4 INCHES OF
 INSULATION? 107.2.1.3 DISCREPANCY.
  
 4D) THE PLANS DO NOT PROVIDE HOW THE ROOF INSULATION
 UNDER THE NEW TOWER WILL BE APPLIED. WILL IT BE ON THE
 EXISTING ROOF DECK OR WILL IT CONTINUE UP AND INTO THE
 TOWER WALLS AND UNDER THE ROOF DECK? 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED. ENERGY 506.3.2
  
 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) TO DATE PRODUCT APPROVALS HAVE NOT BEEN REVIEWED BY
 THE DESIGNER OF RECORD.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. NO APPROVALS WERE SUBMITTED FOR
 THE GLAZED FRENCH DOORS.L
 (B) WINDOWS NOT REVIEWED BY THE DESIGNER OF RECORD.
 (C) WALL LOUVERS A/C FRESH AIR MAKE UP?
 (D) ROOFING PRODUCTS AND ASSEMBLIES NOT REVIEWED BY THE
 DESIGNER OF RECORD, NOTE WHAT ATTACHMENT METHODS WILL
 BE REQUIRED FOR EACH ROOF ZONE.
 (E) SHUTTERS BAHAMA SHUTTERS IN OPEN FIXED POSITION.
 3105.5 RIGID AWNINGS AND CANOPY SHUTTERS. FBC-B
 3105.5.1 LOADS.
 RIGID AWNINGS AND CANOPY SHUTTERS SHALL BE DESIGNED TO
 RESIST THE LOADS SET FORTH IN CHAPTER 16 OF THIS CODE
 EXCEPT THAT STRUCTURES OR PARTS THEREOF WHICH ARE
 INTENDED TO BE REMOVED OR REPOSITIONED DURING PERIODS
 OF HIGH WIND VELOCITY SHALL BE DESIGNED IN THEIR OPEN
 OR EXTENDED POSITION TO DESIGN PRESSURES BASED ON A
 BASIC WIND SPEED OF MINIMUM 115 MPH, 3-SECOND WIND GUST
 WITH APPLICABLE SHAPE FACTORS.
  
 (G) PRE-ENGINEERED A/C STANDS IF APPLICABLE.
  
 7) SHEET A3 DETAIL # 10 INDICATES THE USE OF BEVELED
 WOOD BUCKS WITH THE BACK WINDOW FRAME SUPPORT NOT
 RESTING ON THE BEVELED BUCK. 2010 FBC-B
 1715.5.4.2 UNLESS OTHERWISE TESTED, BUCKS SHALL EXTEND
 BEYOND THE INTERIOR FACE OF THE WINDOW OR DOOR FRAME
 SUCH THAT FULL SUPPORT OF THE FRAME IS PROVIDED.
  
 8) SHEET A4.2 DETAIL # 12 THE RECEPTION DESK SHOWS THE
 COUNTER HEITH OF 42 INCHES HIGH. PLEASE PROVIDE
 COMPLIANCE WITH :
 2010 FL ACCESS. CODE 904.3.3 CHECK WRITING SURFACES.
 WHERE PROVIDED, CHECK WRITING SURFACES SHALL COMPLY
 WITH 902.3.
 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK
 SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34
 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND
 OR
 904.4 SALES AND SERVICE COUNTERS.
 SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH
 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE
 COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR
 SERVICE COUNTER TOP.
 EXCEPTION: IN ALTERATIONS, WHEN THE PROVISION OF A
 COUNTER COMPLYING WITH 904.4 WOULD RESULT IN A
 REDUCTION OF THE NUMBER OF EXISTING COUNTERS AT WORK
 STATIONS OR A REDUCTION OF THE NUMBER OF EXISTING MAIL
 BOXES, THE COUNTER SHALL BE PERMITTED TO HAVE A PORTION
 WHICH IS 24 INCHES (610 MM) LONG MINIMUM COMPLYING WITH
 904.4.1 PROVIDED THAT THE REQUIRED CLEAR FLOOR OR
 GROUND SPACE IS CENTERED ON THE ACCESSIBLE LENGTH OF
 THE COUNTER.
 904.4.1 PARALLEL APPROACH.
 A PORTION OF THE COUNTER SURFACE THAT IS 36 INCHES (915
 MM) LONG MINIMUM AND 36 INCHES (915 MM) HIGH MAXIMUM
 ABOVE THE FINISH FLOOR SHALL BE PROVIDED. A CLEAR FLOOR
 OR GROUND SPACE COMPLYING WITH 305 SHALL BE POSITIONED
 FOR A PARALLEL APPROACH ADJACENT TO THE 36 INCH (915
 MM) MINIMUM LENGTH OF COUNTER.
 EXCEPTION: WHERE THE PROVIDED COUNTER SURFACE IS LESS
 THAN 36 INCHES (915 MM) LONG, THE ENTIRE COUNTER
 SURFACE SHALL BE 36 INCHES (915 MM) HIGH MAXIMUM ABOVE
 THE FINISH FLOOR.
 904.4.2 FORWARD APPROACH.
 A PORTION OF THE COUNTER SURFACE THAT IS 30 INCHES (760
 MM) LONG MINIMUM AND 36 INCHES (915 MM) HIGH MAXIMUM
 SHALL BE PROVIDED. KNEE AND TOE SPACE COMPLYING WITH
 306 SHALL BE PROVIDED UNDER THE COUNTER. A CLEAR FLOOR
 OR GROUND SPACE COMPLYING WITH 305 SHALL BE POSITIONED
 FOR A FORWARD APPROACH TO THE COUNTER.
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  