Notes |
Date |
Text |
2014-10-21 09:24:46 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS, | | SIZES, WINDOW TYPE, ROOM DESIGNATIONS. | | | | 2. FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN | | HEIGHT, NOTE EXISTING CONDITIONS (TYPE OF WINDOW) AND | | OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB 604.1. THE | | CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%. | | | | 3. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R | | 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS | | ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE | | (AVAILABLE IN THE LOBBY AND AT: | | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/SCHEDULE_FOR_INSTALLATION.PDF | | | | IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 606.4, | | PROVIDE CALCULATIONS. | | | | 4. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC | | 109. | | | | 5. ON THE FLOOR PLAN, INCLUDE OCCUPANCY CLASSIFICATION. | | (SINGLE FAMILY & DUPLEX IS R3, THREE UNITS AND MORE IS | | R2). | | | | 6. ON THE FLOOR PLAN, INCLUDE THE PRINTED NAME AND | | SIGNATURE OF THE INDIVIDUAL TAKING RESPONSIBILITY FOR | | THE PLAN, FBC 107. | | | | |
|