Plan Review Notes
Plan Review Notes For Permit 14100468
Permit Number 14100468
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2014-10-17 12:30:14THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE APPLICATION STATES "ADD/RELOCATE 363 SPRINKLER
 HEADS".
  
 ARE THE EXITING SPRINKLER HEADS BEING REPLACED AS PART
 OF THIS APPLICATION?; PLEASE SPECIFY.
  
 IS THERE AN AREAOF NEW/REMODELED CONSTRUCTION THAT
 REQUIRES NEW SPRINKLER COVERAGE?; PLEASE SPECIFY.
  
 THE SUBMITTED PLAN DOES NOT DENOTE WHAT IS EXISTING,
 WHAT IS NEW, OR RELOCATED.
  
 THERE IS NO SYMBOL/TABLE GUIDE.
  
 PROVIDE GREATER DETAIL ADDRESSING THE ABOVE
 REQUIREMENTS.