2014-10-24 13:56:35 | 10/24/2014 | | PROJECT: VINCE CAMUTO SIGN | | PERMIT#: 14100434 | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | ELECTRICAL PLAN REVIEW | | ACTION: DENIED | | | | 1) INDICATE THE LISTING OF THE SIGN. NEC 600.3 | | | | 2) PROVIDE A EXTERNALLY OPERABLE DISCONNECT SWITCH | | WITHIN SIGHT OF THE SIGN. NEC 600.6(A)(1) | | | | 3) INDICATE COMPLIANCE WITH THE FBC-ENERGY 505.2.4 | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | SHEETS FOR COMPARATIVE REVIEW. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|