Plan Review Notes
Plan Review Notes For Permit 14100405
Permit Number 14100405
Review Stop B
Sequence Number 3
Notes
Date Text
2015-01-20 11:44:39****PROVISO****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 INSTALLATION SCHEDULE DID NOT INCLUDE THE FOLLOWING
 INFORMATION:
  
 SHUTTER CONNECTION MOUNTING TYPE (SHOULD CORRELATE WITH
 THE ANCHOR CHARTS ON PAGE 4 OF THE NOA; EITHER C1, C2,
 C3, C4, OR C5)
 ANCHOR SPACING
  
 THEREFORE, INSTALLATION SCHEDULE HAS BEEN REDLINED FOR
 WORST CASE (C5, 5" ANCHOR SPACING)
  
 IF THIS IS NOT ACCEPTABLE, SUBMIT A REVISION WHICH
 INCLUDES A REVISED INSTALLATION SCHEDULE WITH SHUTTER
 CONNECTION MOUNTING TYPE AND ANCHOR SPACING PROPOSED;
 OR, DO NOT PICK UP THIS PERMIT AND RESUBMIT WITH A
 REVISED INSTALLATION SCHEDULE.
  
  