2014-10-21 09:51:18****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REVISE THE FLOOR PLAN TO SHOW WINDOW SIZES.
  
 2. FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN
 HEIGHT, NOTE EXISTING CONDITIONS (TYPE OF WINDOW) AND
 OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB 604.1. THE
 CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%.
  
 TO PROVIDE FURTHER CLARIFICATION REGARDING INFORMATION
 NEEDED FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN
 HEIGHT:
  
 STATE WHAT TYPE OF WINDOW IS THERE NOW IN THE BEDROOMS
 - AWNING, CASEMENT, SINGLE HUNG?
  
 STATE WHAT THE EXISTING CLEAR OPENING DIMENSIONS ARE.
 CLEAR OPENING IS THE OPENING WHICH EXISTS WHEN THE
 WINDOW IS FULLY OPEN.
  
 3. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R
 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS
 ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE
 (AVAILABLE IN THE LOBBY AND AT:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/SCHEDULE_FOR_INSTALLATION.PDF
  
 IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 606.4,
 PROVIDE CALCULATIONS.
  
  
  