Date |
Text |
2014-10-28 09:49:49 | 10/28/2014 |
| PROJECT: MORANO RESIDENCE |
| PERMIT#: 14100394 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) PROVIDE A LIGHTING FIXTURE SCHEDULE INDICATING |
| COMPLIANCE WITH THE FBC-R 402.4.5 RECESSED LIGHTING. |
| AND FBC-R 404.1 LIGHTING EQUIPMENT. RECESSED LUMINAIRES |
| INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE |
| SEALED TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED AND |
| UNCONDITIONED SPACES. A MINIMUM OF 50 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICIENCY. |
| |
| 2) PROVIDE THE LIGHTING PACKAGE SUBMITTALS TO ENSURE |
| COMPLIANCE WITH THE LISTING REQUIREMENTS OF THE NEC |
| 110.3(B) |
| |
| 3) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES |
| INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8) |
| INCLUDING GARAGE DOOR OPENER OUTLETS, SHALL HAVE GROUND |
| FAULT CIRCUIT INTERRUPTER PROTECTION FOR PERSONNEL. NEC |
| 210.8. |
| |
| 4) CHECK TOTAL LOAD ON LIGHTING BRANCH CIRCUIT SWITCH |
| LEGS ON DIMMERS AND VERIFY DIMMER LISTING AND MAX LOAD |
| APPROVED FOR USE. NEC 110.3(B) |
| |
| 5) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS ARE REQUIRED |
| FOR LOW VOLTAGE SYSTEMS SUCH AS BUT NOT LIMITED TO |
| NETWORK, SECURITY, CCTV, & AUDIO/VIDEO. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |