Plan Review Notes For Permit 14100385 |
Permit Number |
14100385 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-10-13 04:33:57 | WPB AMEND.TO 2010 FL. BUILDING CODE SECS. 107.2.1, | | 107.3.5.3. | | 1) OWNER/BUILDER DISCLOSURE FORM IS REQUIRED IN ORDER | | TO APPLY FOR THE PERMIT AS AN OWNER/BUILDER. FL. | | STATUTE 489.103. | | 2) ) CLEARLY IDENTIFY ON BOTH SETS OF PLANS WHERE THE | | INTERIOR PIPING IS CONNECTED TO THE "OUTDOOR TAP". PAGE | | 1 SHOWS THE COLD WATER PIPING CONNECTING TO AN "OUTDOOR | | TAP" AT 3 DIFFERENT LOCATIONS. CLARIFY.SOME OF THE INFO | | IS CUT OFF THE PLAN ON PAGE 1. | | 3) SUBMIT A WATER RISER DIAGRAM FOR REVIEW. | | 4) SUBMIT 2 COPIES OF THE MANUFACTURER'S INSTALLATION | | INSTRUCTIONS FOR THE CPVC PIPE PER WPB AMEND. TO 2010 | | SEC. 107.2.1, 107.3.5.3. | | 5) THE SPACING OF THE SUPPORTS FOR THE PIPING SHALL | | COMPLY W/ THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. | | 7) SHOW ALL PIPE SIZES ON ALL SUBMITTED DRAWINGS. REFER | | TO THE 2010 FBC, RESIDENTIAL, SEC.P2903 & TABLE 2903.2 | | (B). SHOW TOTAL NUMBER OF FIXTURE UNITS. | | 8) IDENTIFY ON THE PLANS IF THE WATER SERVICE LINE FROM | | THE METER TO THE STREET IS BEING REPLACED. | | 9) THE WATER PIPING SHALL BE BONDED PER THE 2008 | | NATIONAL ELECTRIC CODE. | | 10) PAGE #2 - WHERE DO THE HOT AND COLD WATER LINES IN | | THE BATHROOM FOR BEDROOM #5 CONNECT? THE PLAN SHOWS THE | | LINES TERMINATING IN THE BEDROOM. THE PLAN IS VAGUE AND | | THERE MAY BE ADDITIONAL PLAN REVIEW COMMENTS ON THE | | SECOND REVIEW. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | | |
|