Plan Review Notes
Plan Review Notes For Permit 14100385
Permit Number 14100385
Review Stop P
Sequence Number 1
Notes
Date Text
2014-10-13 04:33:57WPB AMEND.TO 2010 FL. BUILDING CODE SECS. 107.2.1,
 107.3.5.3.
 1) OWNER/BUILDER DISCLOSURE FORM IS REQUIRED IN ORDER
 TO APPLY FOR THE PERMIT AS AN OWNER/BUILDER. FL.
 STATUTE 489.103.
 2) ) CLEARLY IDENTIFY ON BOTH SETS OF PLANS WHERE THE
 INTERIOR PIPING IS CONNECTED TO THE "OUTDOOR TAP". PAGE
 1 SHOWS THE COLD WATER PIPING CONNECTING TO AN "OUTDOOR
 TAP" AT 3 DIFFERENT LOCATIONS. CLARIFY.SOME OF THE INFO
 IS CUT OFF THE PLAN ON PAGE 1.
 3) SUBMIT A WATER RISER DIAGRAM FOR REVIEW.
 4) SUBMIT 2 COPIES OF THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS FOR THE CPVC PIPE PER WPB AMEND. TO 2010
 SEC. 107.2.1, 107.3.5.3.
 5) THE SPACING OF THE SUPPORTS FOR THE PIPING SHALL
 COMPLY W/ THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.
 7) SHOW ALL PIPE SIZES ON ALL SUBMITTED DRAWINGS. REFER
 TO THE 2010 FBC, RESIDENTIAL, SEC.P2903 & TABLE 2903.2
 (B). SHOW TOTAL NUMBER OF FIXTURE UNITS.
 8) IDENTIFY ON THE PLANS IF THE WATER SERVICE LINE FROM
 THE METER TO THE STREET IS BEING REPLACED.
 9) THE WATER PIPING SHALL BE BONDED PER THE 2008
 NATIONAL ELECTRIC CODE.
 10) PAGE #2 - WHERE DO THE HOT AND COLD WATER LINES IN
 THE BATHROOM FOR BEDROOM #5 CONNECT? THE PLAN SHOWS THE
 LINES TERMINATING IN THE BEDROOM. THE PLAN IS VAGUE AND
 THERE MAY BE ADDITIONAL PLAN REVIEW COMMENTS ON THE
 SECOND REVIEW.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  