Plan Review Notes
Plan Review Notes For Permit 14100384
Permit Number 14100384
Review Stop E
Sequence Number 1
Notes
Date Text
2014-10-15 13:53:411. PROVIDE PLAN THAT SHOWS EXISTING (E) AND NEW (N) AS
 STATED ON SUBMITTED APPLICATION.
 2 .PLAN TO SHOW MAIN SWITCH EXISTING AND NEW LOCATION.
 3. PROVIDE SIZE OF MAIN SWITCH (AMPERES) AND SIZE OF
 CONDUCTORS SUPPLYING POWER.
 4. PROVIDE GROUNDING ELECTRODE DETAIL. (PER N.E.C.
 250.53)
 5. PROVIDE SIZE OF CONDUCTORS AND LOCATION OF WIRING TO
 BE REPLACED AS STATED ON APPLICATION.
 6. SHOW LOCATION OF SMOKE AND CARBON MONOXIDE DETECTORS
 AS PER FBC R314 & R 315.