2014-12-04 10:34:161) THE SINK NEXT TO THE 3 COMPARTMENT SINK IS MISSING
 FROM THE WATER RISER DIAGRAM.
 2) AS DRAWN, THE SANITARY RISER SHOWS THE GREASE TRAP,
 MOP SINK, FLOOR SINKS, AND HAND SINKS ON A HORIZONTAL
 WET VENT WHICH IS PROHIBITED BY THE 2010 FL. PLUMBING
 CODE (FPC) SEC.909. A VENT DRAWN ON THE WATER CLSET IS
 AN OPTION TO CORRECT THIS VIOLATION. 2ND REQUEST.
 3) SUBMIT MANUF.SPECS/INSTALLATION INSTRUCTIONS FOR THE
 GELATO MACHINE.WPB AMEND TO 2010 FBC SEC.107.2.1. 2ND
 REQUEST.
 4) SUBMIT DETAILS OF THE GREASE INTERCEPTOR. IF THE
 INTERCEPTOR IS CONCRETE, THE DESIGN SHALL COMPLY WITH
 THE 2010 FPC SECS. 1003.5.2, 1003.5.3, AND THE FLORIDA
 ADMINISTRATIVE CODE RULE 64E-6. SUBMIT A DETAIL FOR THE
 INTERCEPTOR. 2ND REQUEST.WPB AMEND. TO 2010 FPC SEC.
 107.2.1. 2ND REQUEST.
 5) SHT. A-6 - THE GREASE INTERCEPTOR CALCULATIONS
 INDICATE 17 SEATS BUT THE PLAN ONLY SHOWS 8. CLARIFY.
 2ND REQUEST.
 6) YOU HAVE PROVIDED CALCULATIONS FOR THE GPM
 DISCHARGING INTO THE INTERCEPTOR. IN ORDER TO FIGURE
 THE TOTAL GPM DISCHARGING INTO THE INTERCEPTOR, ALL THE
 FIXTURES DISCHARGING INTO THE INTERCEPTOR MUST BE
 INCLUDED IN THE CALCULATIONS.YOU HAVE NOT INCLUDED THE
 THREE HAND SINKS. CLARIFY.
 7) A FULL FLOW VALVE IS REQD.ON THE C.W.FEED TO THE
 WATER HEATER. 2010 FPC SEC.606.1.
  