Date |
Text |
2014-12-04 10:34:16 | 1) THE SINK NEXT TO THE 3 COMPARTMENT SINK IS MISSING |
| FROM THE WATER RISER DIAGRAM. |
| 2) AS DRAWN, THE SANITARY RISER SHOWS THE GREASE TRAP, |
| MOP SINK, FLOOR SINKS, AND HAND SINKS ON A HORIZONTAL |
| WET VENT WHICH IS PROHIBITED BY THE 2010 FL. PLUMBING |
| CODE (FPC) SEC.909. A VENT DRAWN ON THE WATER CLSET IS |
| AN OPTION TO CORRECT THIS VIOLATION. 2ND REQUEST. |
| 3) SUBMIT MANUF.SPECS/INSTALLATION INSTRUCTIONS FOR THE |
| GELATO MACHINE.WPB AMEND TO 2010 FBC SEC.107.2.1. 2ND |
| REQUEST. |
| 4) SUBMIT DETAILS OF THE GREASE INTERCEPTOR. IF THE |
| INTERCEPTOR IS CONCRETE, THE DESIGN SHALL COMPLY WITH |
| THE 2010 FPC SECS. 1003.5.2, 1003.5.3, AND THE FLORIDA |
| ADMINISTRATIVE CODE RULE 64E-6. SUBMIT A DETAIL FOR THE |
| INTERCEPTOR. 2ND REQUEST.WPB AMEND. TO 2010 FPC SEC. |
| 107.2.1. 2ND REQUEST. |
| 5) SHT. A-6 - THE GREASE INTERCEPTOR CALCULATIONS |
| INDICATE 17 SEATS BUT THE PLAN ONLY SHOWS 8. CLARIFY. |
| 2ND REQUEST. |
| 6) YOU HAVE PROVIDED CALCULATIONS FOR THE GPM |
| DISCHARGING INTO THE INTERCEPTOR. IN ORDER TO FIGURE |
| THE TOTAL GPM DISCHARGING INTO THE INTERCEPTOR, ALL THE |
| FIXTURES DISCHARGING INTO THE INTERCEPTOR MUST BE |
| INCLUDED IN THE CALCULATIONS.YOU HAVE NOT INCLUDED THE |
| THREE HAND SINKS. CLARIFY. |
| 7) A FULL FLOW VALVE IS REQD.ON THE C.W.FEED TO THE |
| WATER HEATER. 2010 FPC SEC.606.1. |
| |
| PLUMBING PLAN REVIEW |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| 561-805-6692 |
| [email protected] |
| |