Plan Review Notes For Permit 14100359 |
Permit Number |
14100359 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-12-03 12:55:58 | RESUBMITTED COMMENTS: | | | | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO | | | | THE PROPOSED DOOR SWING INTO THE EXIT HALLWAY IS NOT | | ACCEPTABLE. THE BATHROOM DOOR SHALL SWING INTO THE | | BATHROOM, KEEPING CLEAR THE EXIT PATH LEADING TO THE | | REAR EXIT DOOR. | | | | ADD AN ADDITIONAL EXIT SIGN AT THE BEGINNING OF THE | | HALLWAY LEADING TO THE REAR EXIT DOOR. | | | | THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE | | FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND | | COMPLIANCE. | | | | THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE | | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE | | CONSTRUCTION PERIOD. | | | | ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER | | SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND | | BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, | | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE | | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL | | AND COMPLETE PROTECTION IS RETURNED. | | | | |
|