2014-10-23 11:00:191) THE PLANS SHOW THE RESTROOMS LOCATED IN AN AREA THAT
 REQUIRES ACCESS THROUGH THE FOOD PREPARATION AREA.THE
 ROUTE TO PUBLIC TOILET FACILITIES REQUIRED BY SEC.403.3
 OF THE FLORIDA PLUMBING CODE SHALL NOT PASS THROUGH
 KITCHENS, STORAGE ROOMS OR CLOSETS PER SEC.403.3.1.
 2) SUBMIT MANUF. SPECIFICATIONS FOR THE GELATO MACHINE.
 WPB AMEND. TO FBC SEC. 107.2.1.
 3) SUBMIT A LAYOUT OF THE EXISTING FLOOR PLAN. WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 4) SHT. A-3 - THE PLANS REFERENCE THE 2007 FLORIDA
 BUILDING CODE. THE CODE IN EFFECT IS THE 2010 FBC.
 THERE IS NO CHAPTER 11 IN THE 2010 FBC AND THE FIGURE
 NUMBERS LISTED IN THE DETAILS DO NOT EXIST IN THE 2010
 ACCESIBILITY CODE.
 5) SHT. A-5 - DETAIL #3 - PLUMBING FIXTURE MOUNTING
 HEIGHTS - THE WATER CLOSET SHALL BE 16"-18" TO THE
 CENTERLINE FROM ANY SIDE WALL OR PARTITION. FAC
 SEC.604.2.
 6) SUBMIT A WATER RISER DIAGRAM FOR REVIEW. WPB AMEND.
 TO 2010 FBC SEC.107.3.5.1.3.
 7) AS DRAWN, THE SANITARY RISER HAS THE GREASE TRAP AND
 ALL THE OTHER GREASE WASTE FIXTURES ON A WET VENT WHICH
 DOES NOT COMPLY W/ 2010 FPC SEC.909.
 8) CLEANOUTS ARE REQUIRED ON ALL STACKS PER THE 2010
 FPC SEC.708.3.4.
 9) SHT. A-6 - THE GREASE INTERCEPTOR CALCULATIONS
 INDICATE 27 SEATS BUT THE PLAN ONLY SHOWS 8. SUBMIT A
 FULL SEATING PLAN FOR REVIEW. WPB AMEND. TO 2010 FBC
 SEC. 107.2.1.
 10) THE SINK AT THE VESTIBULE SHALL COMPLY W/ THE
 FLORIDA ACCESSIBILITY CODE SEC. 212 & 606.
 11) SUBMIT SPECIFICATIONS FOR THE GREASE TRAP.WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 12) SHOW THE DIMENSIONS OF THE TOILET ROOM NEAR THE
 PREP AREA. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR