2014-10-23 11:00:19 | 1) THE PLANS SHOW THE RESTROOMS LOCATED IN AN AREA THAT |
| REQUIRES ACCESS THROUGH THE FOOD PREPARATION AREA.THE |
| ROUTE TO PUBLIC TOILET FACILITIES REQUIRED BY SEC.403.3 |
| OF THE FLORIDA PLUMBING CODE SHALL NOT PASS THROUGH |
| KITCHENS, STORAGE ROOMS OR CLOSETS PER SEC.403.3.1. |
| 2) SUBMIT MANUF. SPECIFICATIONS FOR THE GELATO MACHINE. |
| WPB AMEND. TO FBC SEC. 107.2.1. |
| 3) SUBMIT A LAYOUT OF THE EXISTING FLOOR PLAN. WPB |
| AMEND. TO 2010 FBC SEC. 107.2.1. |
| 4) SHT. A-3 - THE PLANS REFERENCE THE 2007 FLORIDA |
| BUILDING CODE. THE CODE IN EFFECT IS THE 2010 FBC. |
| THERE IS NO CHAPTER 11 IN THE 2010 FBC AND THE FIGURE |
| NUMBERS LISTED IN THE DETAILS DO NOT EXIST IN THE 2010 |
| ACCESIBILITY CODE. |
| 5) SHT. A-5 - DETAIL #3 - PLUMBING FIXTURE MOUNTING |
| HEIGHTS - THE WATER CLOSET SHALL BE 16"-18" TO THE |
| CENTERLINE FROM ANY SIDE WALL OR PARTITION. FAC |
| SEC.604.2. |
| 6) SUBMIT A WATER RISER DIAGRAM FOR REVIEW. WPB AMEND. |
| TO 2010 FBC SEC.107.3.5.1.3. |
| 7) AS DRAWN, THE SANITARY RISER HAS THE GREASE TRAP AND |
| ALL THE OTHER GREASE WASTE FIXTURES ON A WET VENT WHICH |
| DOES NOT COMPLY W/ 2010 FPC SEC.909. |
| 8) CLEANOUTS ARE REQUIRED ON ALL STACKS PER THE 2010 |
| FPC SEC.708.3.4. |
| 9) SHT. A-6 - THE GREASE INTERCEPTOR CALCULATIONS |
| INDICATE 27 SEATS BUT THE PLAN ONLY SHOWS 8. SUBMIT A |
| FULL SEATING PLAN FOR REVIEW. WPB AMEND. TO 2010 FBC |
| SEC. 107.2.1. |
| 10) THE SINK AT THE VESTIBULE SHALL COMPLY W/ THE |
| FLORIDA ACCESSIBILITY CODE SEC. 212 & 606. |
| 11) SUBMIT SPECIFICATIONS FOR THE GREASE TRAP.WPB |
| AMEND. TO 2010 FBC SEC. 107.2.1. |
| 12) SHOW THE DIMENSIONS OF THE TOILET ROOM NEAR THE |
| PREP AREA. WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| |
| PLUMBING PLAN REVIEW |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |