Plan Review Notes For Permit 14100344 |
Permit Number |
14100344 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-10-24 10:25:47 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | SHEET A - 1.0, DOOR 1654 OPENS INTO AN EXIT CORRIDOR | | IMMEDIATELY NEXT TO THE EXIT DISCHARGE OF ANOTHER | | TENANT SPACE. DOOR LEAF ENCROACHMENT | | DURING ITS SWING, ANY DOOR LEAF IN A MEANS OF EGRESS | | SHALL LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED | | WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, OR A | | LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT MORE | | THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A | | CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN. | | | | THE ABOVE CODE REQUIREMENT DOES NOT ALLOW THE DOOR TO | | OPEN AS PROPOSED. | | | | PLEASE RESUBMIT WITH A CODE COMPLIANT DESIGN. | | |
|