Plan Review Notes
Plan Review Notes For Permit 14100344
Permit Number 14100344
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2014-10-24 10:25:47THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 SHEET A - 1.0, DOOR 1654 OPENS INTO AN EXIT CORRIDOR
 IMMEDIATELY NEXT TO THE EXIT DISCHARGE OF ANOTHER
 TENANT SPACE. DOOR LEAF ENCROACHMENT
 DURING ITS SWING, ANY DOOR LEAF IN A MEANS OF EGRESS
 SHALL LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED
 WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, OR A
 LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT MORE
 THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN.
  
 THE ABOVE CODE REQUIREMENT DOES NOT ALLOW THE DOOR TO
 OPEN AS PROPOSED.
  
 PLEASE RESUBMIT WITH A CODE COMPLIANT DESIGN.
  