2014-10-24 14:47:3210/24/2014
 PROJECT: EDWARDS WILDMAN
 PERMIT#: 14100344
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) VERIFY PRODUCT APPROVAL ON FIRE RATED FLOOR BOX. AND
 PROVIDE A FIRE STOP DETAIL FOR ALL WALL AND FLOOR
 PENETRATIONS OF FIRE RATED ASSEMBLIES. NEC 300.21
  
 2) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 REQUIRED FOR ACCESS CONTROL SYSTEM.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  