Plan Review Notes For Permit 14100293 |
Permit Number |
14100293 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2015-02-19 11:53:02 | 02/19/2015 | | PROJECT: INTERIOR IMPROVEMENTS. #1116 | | PERMIT#: 14100293 | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | 4THELECTRICAL PLAN REVIEW | | ACTION: APPROVED WITH EXCEPTION | | | | PROVIDE ADDITIONAL INFORMATION IN RESPONSE TO THE | | FOLLOWING: | | | | 1) AN ELECTRICAL PERMIT IS REQUIRED. NONE PROVIDED WITH | | THIS SUBMITTAL. | | | | 2) NEC 210.52, 2100.70 | | VERIFY OUTLETS, SWITCHES AND LIGHTING AS REQUIRED ARE | | EXISTING TO REMAIN OR INSTALLED TO BE CODE COMPLIANT. | | | | 3) FBC WPB AMENDMENTS. SECTION 109.3 | | VERIFY VALUATION INDICATED ON APPLICATION. FOR | | PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS | | SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | LAND VALUE. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|