Plan Review Notes For Permit 14100293 |
Permit Number |
14100293 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2015-01-21 08:55:27 | 1/21/2015 | | PROJECT: INTERIOR IMPROVEMENTS. #1116 | | PERMIT#: 14100293 | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | 2ND ELECTRICAL PLAN REVIEW | | ACTION: DENIED | | | | PROVIDE ADDITIONAL INFORMATION IN RESPONSE TO THE | | FOLLOWING: | | | | 1) AN ELECTRICAL PERMIT IS REQUIRED. NONE PROVIDED IN | | THIS SUBMITTAL. | | | | 2) VERIFY SMOKE DETECTORS AS REQUIRED. FBC-RESIDENTIAL | | 314 AND 315. | | | | 3) VERIFY REUIRED WORKING CLEARANCES. NEC 110.26 | | | | 4) BOND METAL FRAMING AS REQUIRED. FBC 2704 | | | | 5) PROVIDE A REVISED PANEL SCHEDULE TO INDICATE ANY NEW | | OR ALTERED CIRCUITS. NEC 408.4 | | | | 6) PROVIDE A FIXTURE SCHEDULE INDICATING COMPLIANCE | | WITH NEC 110.3 (B) | | | | 7) PROVIDE ADDITIONAL DETAIL ON THE METHODS AND | | MATERIALS PROPOSED FOR THE INSTALLATION OF THE CEILING | | FAN IN THE LIVING ROOM. | | | | 8) PROVIDE ARC FAULT PROTECTION ON ALL NEW ELECTRICAL | | CIRCUITRY. NEC 210.12 | | | | 9) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER | | RESISTANT NEC 406.11 | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|