Plan Review Notes
Plan Review Notes For Permit 14100293
Permit Number 14100293
Review Stop E
Sequence Number 3
Notes
Date Text
2015-01-21 08:55:271/21/2015
 PROJECT: INTERIOR IMPROVEMENTS. #1116
 PERMIT#: 14100293
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 PROVIDE ADDITIONAL INFORMATION IN RESPONSE TO THE
 FOLLOWING:
  
 1) AN ELECTRICAL PERMIT IS REQUIRED. NONE PROVIDED IN
 THIS SUBMITTAL.
  
 2) VERIFY SMOKE DETECTORS AS REQUIRED. FBC-RESIDENTIAL
 314 AND 315.
  
 3) VERIFY REUIRED WORKING CLEARANCES. NEC 110.26
  
 4) BOND METAL FRAMING AS REQUIRED. FBC 2704
  
 5) PROVIDE A REVISED PANEL SCHEDULE TO INDICATE ANY NEW
 OR ALTERED CIRCUITS. NEC 408.4
  
 6) PROVIDE A FIXTURE SCHEDULE INDICATING COMPLIANCE
 WITH NEC 110.3 (B)
  
 7) PROVIDE ADDITIONAL DETAIL ON THE METHODS AND
 MATERIALS PROPOSED FOR THE INSTALLATION OF THE CEILING
 FAN IN THE LIVING ROOM.
  
 8) PROVIDE ARC FAULT PROTECTION ON ALL NEW ELECTRICAL
 CIRCUITRY. NEC 210.12
  
 9) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT NEC 406.11
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  