2014-10-14 09:03:55 | SENT TO MISC. 2 |
| |
| |
2014-10-14 09:03:28 | 10/14/2014 |
| PROJECT: 701 OLIVE |
| PERMIT#: 14100293 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| BY THE BUILDING OFFICIAL. WPB AMENDMENTS TO FBC 107.2.1 |
| |
| 2) MINIMUM ELECTRICAL PLAN REVIEW CRITERIA SHALL |
| INCLUDE BUT NOT BE LIMITED TO THE FOLLOWING: ELECTRIC |
| SERVICE RISER WITH WIRE SIZES, CONDUIT AND GROUNDING |
| DETAIL. COMPLETE LOAD CALCULATIONS, AND PANEL |
| SCHEDULES. WPB AMENDMENTS TO FBC 107.3.5.3 RESIDENTIAL |
| (ONE AND TWO-FAMILY). REVISE PLANS TO INCLUDE THE |
| LOCATION OF ELECTRICAL PANELS AND THE PANEL SCHEDULES |
| FOR THE AFFECTED PANELS. |
| |
| 3) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS |
| TO FBC 107.2.1 |
| |
| 4) AN ELECTRICAL PERMIT IS REQUIRED FROM A QUALIFIED |
| ELECTRICAL CONTRACTOR FOR THE ELECTRICAL SCOPE OF WORK. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |