2014-10-13 06:00:41****PROVISO****
 1) SEDIMENT TRAPS REQD. ON EQUIP./ APPLIANCE PER 2010
 FUEL GAS CODE SEC.408.4.
 2) REGULATORS TO BE VENTED OUTDOORS IF EQUIPPED W/VENT
 PER 2010 FGC SEC. 410.3.
 3) A LISTED SHUTOFF VALVE IS REQD. IMMEDIATELY AHEAD OF
 EACH MP REGULATOR. 2010 FGC SEC.409.4
 4) PIPING IN SUBFLOOR SHALL COMPLY W/2010 FGC SEC. 404.
  