Plan Review Notes
Plan Review Notes For Permit 14100194
Permit Number 14100194
Review Stop B
Sequence Number 1
Notes
Date Text
2014-11-07 09:22:43BUILDING PLAN REVIEW
 PERMIT: 14100194
 ADD: 3416 S. DIXIE HWY
 CONT: JACOB ERECTING
 TEL: (561)741-1818
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. NOV. 07/2014
 ACTION: DENIED
  
 1) PLEASE PROVIDE A SITE PLAN WITH THE PROPOSED
 LOCATION OF THE BUILDING ON THE LOT AND THE DISTANCE
 FROM PROPERTY LINES.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION,107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 1. SITE PLAN & REQUIREMENTS:
 PARKING
 FIRE ACCESS
 VEHICLE LOADING
 DRIVING/TURNING RADIUS
 FIRE HYDRANT/WATER SUPPLY/POST INDICATOR VALVE (PIV)
 SET BACK/SEPARATION (ASSUMED PROPERTY LINES)
  
 2) MISSING SOILS REPORT. PLEASE PROVIDE WHAT THE
 MINIMUM SAFE BEARING VALUE IS. 2010 FBC-B 1803.5.2
 QUESTIONABLE SOIL.WHERE THE CLASSIFICATION, STRENGTH OR
 COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A
 LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE
 PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION
 BE CONDUCTED.
  
 3) THIS IS A NEW BUILDING BUT NO ENERGY CALCULATIONS
 WERE PROVIDED. 2010 FBC- ENERGY 103.2/ TABLE 103.2.1 OR
 103.2.2.2.
  
 4) MISSING WIND PRESSURES FOR COMPONENTS AND CLADDING.
 SHEET S1 LIST THE WIND DESIN CRITERIA BUT THE PRESSURES
 FOR COMPONENTS AND CLADDING ARE MISSING FOR ROOF ZONES
 1,2, & 3 AS WELL AS WALL ZONES 4 & 5.
  
 5) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING.FLORIDA DEPARTMENT OF
 COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 6) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) SHEET LS-1.0 INDICATES A 1 HOUR TENANT SEPERATION
 WALL SEE A-5 DETAIL # 2. PLEASE NOTE THE DETAIL
 INDICATES FASTENING THE TOP TRACK TO THE ROOF DECK AND
 TO CAULK BOTH SIDES OF WALL WITH # HW-D-0200. PLEASE
 PROVIDE INFORMATION ON CAULK. THIS HAS TO BE A FLEXIBLE
 JOINT BEING A CONNECTION TO DISSIMILAR MATERIALS AND
 FLEXIBLE SINCE THE ROOF LOADING MAY CHANGE.
 2010 FBC-B
 714.1 GENERAL.
 JOINTS INSTALLED IN OR BETWEEN FIRE-RESISTANCE-RATED
 WALLS, FLOOR OR FLOOR/CEILING ASSEMBLIES AND ROOFS OR
 ROOF/CEILING ASSEMBLIES SHALL BE PROTECTED BY AN
 APPROVED FIRE-RESISTANT JOINT SYSTEM DESIGNED TO RESIST
 THE PASSAGE OF FIRE FOR A TIME PERIOD NOT LESS THAN THE
 REQUIRED FIRE-RESISTANCE RATING OF THE WALL, FLOOR OR
 ROOF IN OR BETWEEN WHICH IT IS INSTALLED.
 FIRE-RESISTANT JOINT SYSTEMS SHALL BE TESTED IN
 ACCORDANCE WITH SECTION 714.3. THE VOID CREATED AT THE
 INTERSECTION OF A FLOOR/CEILING ASSEMBLY AND AN
 EXTERIOR CURTAIN WALL ASSEMBLY SHALL BE PROTECTED IN
 ACCORDANCE WITH SECTION 714.4.
  
 8) SHEET LS-1.0 THE 1-HOUR FIRE SEPARATION WALL WILL
 NEED LABELING SEEFBC-B 713.6. SUCH IDENTIFICATION SHALL
 BE ABOVE ANY DECORATIVE CEILING AND IN CONCEALED
 SPACES. SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS:
 ?FIRE AND SMOKE BARRIER ? PROTECT ALL OPENINGS.?
  
 9) SHEET LS-1.0 THE LARGER OF THE TWO TENANT SPACES
 REFLECTS A OCCUPANT LOAD > THAN 49 REQUIRING 2 EXITS
 FBC TABLE 1015.1.). THE REAR EXIT OF THIS SPACE IS A
 REQUIRED EXIT WITH AN OCCUPANT LOAD APPROX. 81
 OCCUPANTS. NOTE THE PLANS INDICATE INSWING DOOR ,
 SECTION FBC-B 1008.1.2 REQUIRES DOORS SHALL SWING IN
 THE DIRECTION OF EGRESS TRAVEL WHERE SERVING AN
 OCCUPANT LOAD OF 50 OR MORE PERSONS OR A GROUP H
 OCCUPANCY.
 PLEASE ALSO NOTE, NOT HAVING A SITE PLAN EXTERIOR DOORS
 CAN NOT SWING OVER PROPERTY LINES. FBC-B 3202.2.
  
 10) LS-1.0 THE DESIGNER OF RECORD HAS ELECTED TO DESIGN
 THIS BUILING AS A IIIA TYPE BUILDING (PROTECTED),
 PLEASE PROVIDE THE 1 HOUR FIRE RATING OF THE PRIMARY
 STRUCTURAL FRAME, 2 HR EXTERIOR WALLS SEE FOOTNOTES F &
 G, AND 1 HOUR FOR ROOF CONSTRUCTION AND SECONDARY
 MEMBERS.
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  