2014-11-10 18:12:55****PROVISO****
 ****ISSUED AT CONTRACTOR'S RISK****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REVISE PLAN TO INCLUDE WIND AND DESIGN CRITERIA, FBC
 1609 (OR SUBMIT A LETTER FROM ENGINEER).
  
 "WIND DESIGN CRITERIA" SHOULD INCLUDE WIND SPEED AND
 EXPOSURE CLASSIFICATION.
  
 EXPOSURE CLASSIFICATION IS REQUIRED TO BE EXPOSURE D
 DUE TO THE LOCATION. WIND DESIGN CRITERIA SHOULD BE A
 MINIMUM OF 150MPH (RISK CATEGORY 1).
  
  
  