2014-10-06 10:24:06 | BUILDING PLAN REVIEW |
| PERMIT:14100159 |
| ADD: 605 GREEN SPRINGS PLACE UNITS # (605,606, 607 & |
| 608) |
| CONT: GARABAR ROOFING |
| TEL: (561) 336-6798 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. OCT. 06/ 2014 |
| ACTION: DENIED |
| |
| ROOF OVER |
| |
| 1) THE 2010 FL EXST BLDG CODE SECTION 611.3 |
| 611.3 RECOVERING VERSUS REPLACEMENT. |
| NEW ROOF COVERINGS SHALL NOT BE INSTALLED WITHOUT FIRST |
| REMOVING ALL EXISTING LAYERS OF ROOF COVERINGS WHERE |
| ANY OF THE FOLLOWING CONDITIONS OCCUR: |
| |
| 1. WHERE THE EXISTING ROOF OR ROOF COVERING IS WATER |
| SOAKED OR HAS DETERIORATED TO THE POINT THAT THE |
| EXISTING ROOF OR ROOF COVERING IS NOT ADEQUATE AS A |
| BASE FOR ADDITIONAL ROOFING. THE MOISTURE TEST |
| PERFORMED INDICATES THE MOISTURE LEVEL IS ABOVE THE |
| REQUIRED 5% BY SECTION 1521.12 PROTOCAL TAS-126. |
| |
| 2. DOES NOT APPLY. WHERE THE EXISTING ROOF COVERING IS |
| WOOD SHAKE, SLATE, CLAY, CEMENT OR ASBESTOS-CEMENT |
| TILE. |
| |
| 3.WILL NEED TO VERIFY HOW MANY ROOFING ROOFING |
| APPLICATIONS ARE ON THE ROOF ALREADY, THE CORING TEST |
| DOES NOT INDICATE. WHERE THE EXISTING ROOF HAS TWO OR |
| MORE APPLICATIONS OF ANY TYPE OF ROOF COVERING. |
| |
| WILL NEED TO VERIFY THERE IS NO BLISTERING. 4. WHEN |
| BLISTERS EXIST IN ANY ROOFING, UNLESS BLISTERS ARE CUT |
| OR SCRAPED OPEN AND REMAINING MATERIALS SECURED DOWN |
| BEFORE APPLYING ADDITIONAL ROOFING. |
| |
| NO PULL TEST HAS BEEN PREFORMED IN THE WATER DAMAGED |
| AREAS. 5.WHERE THE EXISTING ROOF IS TO BE USED FOR |
| ATTACHMENT FOR A NEW ROOF SYSTEM AND COMPLIANCE WITH |
| THE SECUREMENT PROVISIONS OF SECTION 1504.1 CAN NOT BE |
| MET. |
| |
| SUBMITTED NOA: 13-0603.05 |
| GAF EVERGUARD TPO SINGLE PLY ROOFING SYSTEM FOR RECOVER |
| DECKS. |
| PAGE 17 OF 18. |
| MEMBRANE TYPE SINGLE PLY, THERMOPLASTIC, TPO |
| DECK TYPE 71: RECOVER NON-INSULATEDDECK DESCRIPTION : |
| 2500 PSI STRUCTURAL CONCRETE OR MINIMUM 22 GAUGE STEEL |
| DECK |
| SYSTEM TYPE F: MEMBRANE ADHERED TO EXISTING GRANULAR |
| ROOF SYSTEM. |
| |
| NO PULL TEST PROVIDED SHOWING THE EXISTING ROOF |
| APPLICATION IS ADHERRED TO DECK. |
| THE OTHER ISSUE IS THIS NOA IS FOR A STRUCTURAL |
| CONCRETE DECK OR MINIMUM 22 GAUGE STEEL DECK. THE |
| MOISTURE TEST PREFORMED INDICATES THIS IS A LIGHT |
| WEIGHT CONCRETE DECK, NON-STRUCTURAL, NOR HAS THE DECK |
| TYPE BEEN CONFIRMED 22 GAUGE STEEL. THE PULL TEST WILL |
| CONFIRM THE 5TH REQUIREMENT OF IF THE EXISTING |
| LIGHTWEIGHT DECK WILL BE SOUND OR IF THE ATTACHMENT |
| WILL NEED TO PENETRATE THE METAL DECK,DIA. & LENGHT OF |
| FASTENER, DIAMETER OF WASHER, AND THE DENSITY OF |
| FASTENERS REQUIRED TO MEET THE REQUIRED WIND DESIGN & |
| WIND PRESSURES. |
| |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |