Plan Review Notes
Plan Review Notes For Permit 14100100
Permit Number 14100100
Review Stop B
Sequence Number 3
Notes
Date Text
2015-02-09 09:56:21****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 COMMENTS FROM PREVIOUS LIST, NOT ADDRESSED:
  
 1. SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE
 WITH THE ANCHOR CHARTS ON SHEET 11 (FOR EXAMPLE, 1 TOP,
 2 BOTTOM, ETC.). FOR TAPCONS, MASONRY SUBSTRATE, NOT
 ALL CONNECTION TYPES ARE ALLOWED AND ALL REQUIRE ANCHOR
 SPACING OF 4 1/2" OR 5". 12" IS PROPOSED.
  
 2. SUBSTRATE STATED IS "CONC. BLK". MOST CBS STRUCTURES
 HAVE A CONCRETE TOP SUBSTRATE, MASONRY BOTTOM
 SUBSTRATE.
  
 NEW COMMENT:
  
 3. THE APPLICATION STATES THAT SCOPE IS TO INSTALL 2
 WINDOWS AND 2 DOORS, BUT THE PLAN DOES NOT INDICATE
 WHICH WINDOWS ARE INCLUDED IN THE SCOPE. FBC 107,
 REVISE PLAN TO INDICATE WHICH WINDOWS ARE INCLUDED IN
 THE SCOPE OF THIS PERMIT OR REVISE APPLICATION.
  
 4. VALUE IS TOO LOW, FBC 109. VALUE SHOULD INCLUDE THE
 VALUE OF LABOR, MATERIALS, OVERHEAD, PROFIT,
 ENGINEERING/PLANS, EVEN IF PROVIDED BY OTHERS, FBC 109.
  
 5. IF THE SHUTTER INSTALLATION SCHEDULE IS NOT
 CORRECTED WHEN RESUBMITTED, THIS PERMIT WILL BE ISSUED
 WITH PROVISO THAT A REVISION WILL BE REQUIRED PRIOR TO
 FIRST INSPECTION, FBC 107.
  
 6. RESUBMITTALS ARE TO BE DONE THROUGH THE FRONT
 COUNTER WITH A RESUBMITTAL FORM. FAILURE TO FOLLOW THE
 PROCEDURES MAY RESULT IN PLANS NOT BEING ROUTED AND
 REVIEWED TIMELY, OR IN PLANS MISPLACED OR LOST. THE
 RESUBMITTAL FORM AND TRACKING THROUGH THE FRONT COUNTER
 ENSURES THAT YOUR RESUBMITTAL IS REVIEWED AND FILED
 CORRECTLY AND WITHIN OUR TARGET TURNAROUND TIMES.
  
  
  
  