Notes
Date Text
2015-01-23 16:41:52****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE
 WITH THE ANCHOR CHARTS ON SHEET 11 (FOR EXAMPLE, 1 TOP,
 2 BOTTOM, ETC.). FOR TAPCONS, MASONRY SUBSTRATE, NOT
 ALL CONNECTION TYPES ARE ALLOWED AND ALL REQUIRE ANCHOR
 SPACING OF 4 1/2" OR 5". 12" IS PROPOSED.
  
 2. SUBSTRATE STATED IS "CONC. BLK". MOST CBS STRUCTURES
 HAVE A CONCRETE TOP SUBSTRATE, MASONRY BOTTOM
 SUBSTRATE.
  
 3. PLEASE RE PRINT THE SHUTTER PRODUCT APPROVALS AS
 THEY ARE NOT LEGIBLE AND/OR COMPLETE, FBC 107. AT
 APPEARS THAT ONLY HALF OF THE PAGE PRINTED.
  
  