Plan Review Notes For Permit 14091093 |
Permit Number |
14091093 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-10-22 15:30:10 | 2ND REVIEW: FBC 2010 | | | | PROVISO: SUBMIT A REVISION FOR THE INFORMATION BELOW: | | FBC 107.3.5 STRUCTURAL PLAN REVIEW CRITERIA SHALL | | INCLUDE WALL SYSTEMS. SPECIFY THE SPACING OR CLARIFY | | THE QUANTITY AND TYPE OF THE "TITEN" ANCHORS IN THE TOP | | AND BOTTOM PLATES IN WALL SECTION A. ADDITIONALLY, | | SPECIFY ANY CONNECTION AT THE ENDS/SIDES OF EACH WALL | | TO THE EXISTING STRUCTURE. PLEASE NOTE THE EXISTING | | FOUNDATION ON SECTIONS A APPREARS TO BE LARGER AND TO | | HAVE MORE RE-INFORCING THAN THE SECTION ON THE ORIGINAL | | CONSTRUCTION PLANS ON FILE. THAT PLAN SHOW THE FOOTING | | TO BE 8X8 W/1#5. | | | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | |
|