Plan Review Notes For Permit 14091088 |
Permit Number |
14091088 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-11-08 16:16:50 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. EDGE DISTANCE PROPOSED (2") DOES NOT MEET THE | | REQUIREMENTS OF THE PRODUCT APPROVAL, SEE ANCHOR | | CHARTS. FBC 2010 RESIDENTIAL 301. | | | | 2. SHUTTER SPAN STATED IS 100" FOR A 108" HIGH OPENING, | | HORIZONTAL INSTALLATION. ACCORDIONS ARE TYPICALLY | | INSTALLED VERTICALLY, AND SPAN IS BLADE LENGTH. RATHER | | THAN SPECIFYING "WALL" AND "DECO FLOOR", USE THE NAMING | | CONVENTION IN THE PRODUCT APPROVAL (C1 - C5) TO SPECIFY | | WHICH MOUNTING TYPE IS PROPOSED. | | | | 3. THE SITE SPECIFIC DOES NOT STATE WIND DESIGN | | CRITERIA, AND THE ENGINEERING IS NOT HIGHLIGHTED OR | | MARKED. REVISE SITE SPECIFIC TO INCLUDE WIND DESIGN | | CRITERIA (WIND SPEED AND EXPOSURE CLASSIFICATION). | | | 2014-10-29 15:42:32 | 2ND CHECKLIST | | | | 1. PROVIDE TWO UP TO DATE SURVERYS SHOWING THE LOCATION | | OF SCREEN WALL. |
|