Date |
Text |
2014-10-25 07:57:33 | 1) SHT.G102 - PLUMBING FIXTURE TABLE - INDICATE ON THE |
| PLAN HOW YOU ARE COMPLYING WITH SEC. 410.1 OF THE 2010 |
| FLORIDA PLUMBING CODE FOR THE REDUCTION OF THE REQUIRED |
| NUMBER OF DRINKING FOUNTAINS. |
| 2) PLEASE PROVIDE A NARRATIVE EXPLAINING THE BED |
| TABULATION TABLE AND HOW TO READ IT. WPB AMEND. TO 2010 |
| FBC SEC.107.2.1. WHAT DO THE LETTERS "P" & "SP" |
| 3) SHT. E-A001 - MOUNTING HT. DETAILS SHOW VERTICAL |
| GRAB BARS. GRAB BARS MUST BE INSTALLED IN THE |
| HORIZONTAL POSITION PER THE 2010 FL. ACCESSIBILITY CODE |
| SEC.609.4.VERTICAL GRABS BARS ARE NOT ACCEPTABLE. |
| 4) SHT.E-A001. - THE LIP OF THE URINAL SHALL BE A MAX. |
| OF 17" ABOVE THE FINISHED FLOOR PER THE 2010 FAC |
| SEC.605.2. |
| 5) SHT.E-A001 - THE ACCESSIBLE DRINKING FOUNTAINS SHALL |
| COMPLY W/ THE FAC SECS. 306.2, 306.3, & 602 FOR KNEE & |
| TOE CLEARANCES. SHOW THE CLEARANCES ON THE DETAIL. |
| 6) SHT.E-A101 - TOILET ROOM #142 DOES NOT APPEAR TO |
| MEET THE SIZE & FIXTURE CLEARANCES OF THE 2010 FL. |
| ACCESSIBILITY CODE. PROVIDE DIMENSIONS AND CLEAR FLOOR |
| SPACE FOR FIXTURES AND THE REQUIRED 5 FT TURNING |
| DIAMETER OR T-TURN. |
| 7) THE WASHERS & DRYERS IN THE LAUNDRY ROOMS SHALL |
| COMPLY W/ SECS. 214 & 611 OF THE 2010 FAC. |
| 8) PROVIDE A PLAN VIEW OF THE ACCESSIBLE SHOWERS. SHOW |
| ALL DIMENSIONS AND DETAILS. WPB AMEND. TO 2010 FBC SEC. |
| 107.2.1. |
| 9) SHT. E-A001 - THE TOILET PAPAER DISPENSERS SHALL |
| COMPLY W/ 2010 FAC. SEC.604.7. |
| 10) SHT. E-A402 - DETAILS # 15, #16, & 17 - THE SINKS |
| IN THESE AREAS SHALL COMPLY W/ 2010 FAC - SECS. 212 & |
| 606. |
| 11) SHT. E-A403 - NOURISHMENT RMS. #144 & 145 - THE |
| SINKS AND OTHER ELEMENTS IN THIS ROOM SHALL COMPLY W/ |
| 2010 FAC SECS.212 & 606, 804, 805. |
| 12) THE ISLAND SINKS SHALL COMPLY W/ THE HEIGHT REQS. |
| OF THE 2010 FAC SECS. 212.3 & 606. |
| 13) SHT. E-A412 - ATLEAST ONE SINK IN THE SALON SHALL |
| COMPLY W/ 2010 FAC SECS.212.3 & 606. SEE DETIALS #3 & # |
| 7. |
| 14) IDENTIFY THE AREAS ON THE PLANS WHERE THE BARRIER |
| FREE SINKS WILL BE INSTALLED. WPB AMEND. TO 2010 FBC |
| SEC. 107.2.1. |
| 15) SHT. E-P501 - SIZE ALL SECTIONS OF THE DWV SYSTEM |
| ON ALL THE RISERS. WPB AMEND. TO 2010 FBC SEC. 107.2.1 |
| 16) SHT. E-P202 - RM. #245 - THE SANITARY RISER SHOWS |
| PIPING FOR A PIECE OF EQUIPMENT WITH QUESTION MARKS FOR |
| IT. CLARIFY THE PIECE OF EQUIPMENT. IF IT IS A PEDICURE |
| CHAIR, SUBMIT THE MANUF. SPECIFICATIONS FOR THE |
| ITEM.WPB AMEND. TO 2010 FBC SEC. 107.2.1 |
| 17) SHT.E-P501 - RISER FOR RMS. 155 & 156 - AS |
| DESIGNED, A URINAL IS ON A WET VENT. URINALS ARE NOT |
| PERMITTED ON A WET VENT PER THE 2010 FPC SEC. 909.1. |
| THE RISER ALSO SHOWS A DRY VENT NEXT TO FIXTURE L-3. |
| EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL |
| CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN |
| PIPE. 2010 FPC SEC.905.3. |
| 18) SHT. E-P502 - IDENTIFY THE ROOM NUMBERS THAT |
| CORRELATE WITH THE APPLICABLE WATER RISER. |
| 19) IDENTIFY AND SIZE ALL LINES ON THE WATER RISERS |
| INCLUDING THE EXISTING. WPB AMEND. TO 2010 FBC SEC. |
| 107.2.1. |
| |