Plan Review Notes
Plan Review Notes For Permit 14091069
Permit Number 14091069
Review Stop P
Sequence Number 1
Notes
Date Text
2014-10-25 07:57:331) SHT.G102 - PLUMBING FIXTURE TABLE - INDICATE ON THE
 PLAN HOW YOU ARE COMPLYING WITH SEC. 410.1 OF THE 2010
 FLORIDA PLUMBING CODE FOR THE REDUCTION OF THE REQUIRED
 NUMBER OF DRINKING FOUNTAINS.
 2) PLEASE PROVIDE A NARRATIVE EXPLAINING THE BED
 TABULATION TABLE AND HOW TO READ IT. WPB AMEND. TO 2010
 FBC SEC.107.2.1. WHAT DO THE LETTERS "P" & "SP"
 3) SHT. E-A001 - MOUNTING HT. DETAILS SHOW VERTICAL
 GRAB BARS. GRAB BARS MUST BE INSTALLED IN THE
 HORIZONTAL POSITION PER THE 2010 FL. ACCESSIBILITY CODE
 SEC.609.4.VERTICAL GRABS BARS ARE NOT ACCEPTABLE.
 4) SHT.E-A001. - THE LIP OF THE URINAL SHALL BE A MAX.
 OF 17" ABOVE THE FINISHED FLOOR PER THE 2010 FAC
 SEC.605.2.
 5) SHT.E-A001 - THE ACCESSIBLE DRINKING FOUNTAINS SHALL
 COMPLY W/ THE FAC SECS. 306.2, 306.3, & 602 FOR KNEE &
 TOE CLEARANCES. SHOW THE CLEARANCES ON THE DETAIL.
 6) SHT.E-A101 - TOILET ROOM #142 DOES NOT APPEAR TO
 MEET THE SIZE & FIXTURE CLEARANCES OF THE 2010 FL.
 ACCESSIBILITY CODE. PROVIDE DIMENSIONS AND CLEAR FLOOR
 SPACE FOR FIXTURES AND THE REQUIRED 5 FT TURNING
 DIAMETER OR T-TURN.
 7) THE WASHERS & DRYERS IN THE LAUNDRY ROOMS SHALL
 COMPLY W/ SECS. 214 & 611 OF THE 2010 FAC.
 8) PROVIDE A PLAN VIEW OF THE ACCESSIBLE SHOWERS. SHOW
 ALL DIMENSIONS AND DETAILS. WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 9) SHT. E-A001 - THE TOILET PAPAER DISPENSERS SHALL
 COMPLY W/ 2010 FAC. SEC.604.7.
 10) SHT. E-A402 - DETAILS # 15, #16, & 17 - THE SINKS
 IN THESE AREAS SHALL COMPLY W/ 2010 FAC - SECS. 212 &
 606.
 11) SHT. E-A403 - NOURISHMENT RMS. #144 & 145 - THE
 SINKS AND OTHER ELEMENTS IN THIS ROOM SHALL COMPLY W/
 2010 FAC SECS.212 & 606, 804, 805.
 12) THE ISLAND SINKS SHALL COMPLY W/ THE HEIGHT REQS.
 OF THE 2010 FAC SECS. 212.3 & 606.
 13) SHT. E-A412 - ATLEAST ONE SINK IN THE SALON SHALL
 COMPLY W/ 2010 FAC SECS.212.3 & 606. SEE DETIALS #3 & #
 7.
 14) IDENTIFY THE AREAS ON THE PLANS WHERE THE BARRIER
 FREE SINKS WILL BE INSTALLED. WPB AMEND. TO 2010 FBC
 SEC. 107.2.1.
 15) SHT. E-P501 - SIZE ALL SECTIONS OF THE DWV SYSTEM
 ON ALL THE RISERS. WPB AMEND. TO 2010 FBC SEC. 107.2.1
 16) SHT. E-P202 - RM. #245 - THE SANITARY RISER SHOWS
 PIPING FOR A PIECE OF EQUIPMENT WITH QUESTION MARKS FOR
 IT. CLARIFY THE PIECE OF EQUIPMENT. IF IT IS A PEDICURE
 CHAIR, SUBMIT THE MANUF. SPECIFICATIONS FOR THE
 ITEM.WPB AMEND. TO 2010 FBC SEC. 107.2.1
 17) SHT.E-P501 - RISER FOR RMS. 155 & 156 - AS
 DESIGNED, A URINAL IS ON A WET VENT. URINALS ARE NOT
 PERMITTED ON A WET VENT PER THE 2010 FPC SEC. 909.1.
 THE RISER ALSO SHOWS A DRY VENT NEXT TO FIXTURE L-3.
 EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL
 CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN
 PIPE. 2010 FPC SEC.905.3.
 18) SHT. E-P502 - IDENTIFY THE ROOM NUMBERS THAT
 CORRELATE WITH THE APPLICABLE WATER RISER.
 19) IDENTIFY AND SIZE ALL LINES ON THE WATER RISERS
 INCLUDING THE EXISTING. WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
  
 PLUMBING PLAN REVIEW