2014-12-31 09:12:30NEW SINGLE FAMILY RESIDENCE (R3) THIRD MECHANICAL
 REVIEW COMMENTS.
 CODE: 2010 FBC
  
 1- NEW EQUIPMENT SIZING CALCULATIONS WERE PROVIDED. NEW
 CALCULATIONS ARE MISSING THE WORKSHEET FOR ENTIRE
 HOUSE. OLD CALCULATIONS ARE DONE FOR WORST CASE
 SCENARIO (NE, SE, SW AND NW). THIS IS NOT ALLOWED. THE
 EQUIPMENT SIZING CALCULATIONS NEED TO BE REVISED. THEY
 NEED TO BE DONE BASED ON THE ACTUAL BUILDING
 ORIENTATION OF THE HOUSE AS REQUIRED BY SEC. 403.6 OF
 2010 FBC-ENERGY CONSERVATION. PROVIDE TWO COMPLETE
 REVISED EQUIPMENT SIZING CALCULATIONS.
 (REPEAT COMMENT. NOT ADDRESSED. NO CALCULATIONS WERE
 SUBMITTED THIS TIME).
  
 2- A/C PLAN: EQUIPMENT LISTED ON THE A/C PLAN DOESN'T
 MATCH ANY EQUIPMENT LISTED ON THE EQUIPMENT SIZING
 CALCULATIONS SUBMITTED ON PREVIOUS SUBMITTALS.
 ***NOTE: THERE WERE NOT NEW EQUIPMETN CALCUALTIONS
 SUBMITTED AT THIS TIME TO ADDRESS COMMENT #1 ABOVE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  