2014-12-09 16:03:05NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC
  
 1- NEW EQUIPMENT SIZING CALCULATIONS WERE PROVIDED. NEW
 CALCULATIONS ARE MISSING THE WORKSHEET FOR ENTIRE
 HOUSE. OLD CALCULATIONS ARE DONE FOR WORST CASE
 SCENARIO (NE, SE, SW AND NW). THIS IS NOT ALLOWED. THE
 EQUIPMENT SIZING CALCULATIONS NEED TO BE REVISED. THEY
 NEED TO BE DONE BASED ON THE ACTUAL BUILDING
 ORIENTATION OF THE HOUSE AS REQUIRED BY SEC. 403.6 OF
 2010 FBC-ENERGY CONSERVATION. PROVIDE TWO COMPLETE
 REVISED EQUIPMENT SIZING CALCULATIONS.
  
 2- A/C PLAN:
 A) PROVIDE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. 107.2.1
 OF CITY AMENDMENTS TO FBC.
  
 B) PROVIDE THE EQUIPMENT INFORMATION ON THE A/C PLAN AS
 REQUIRED BY SEC. 107.3.5.3(10) OF CITY AMENDMENTS.
 ***NOTE: COORDINATE WITH EQUIPMENT SPECIFIED ON THE
 REVISED EQUIPMENT SIZING CALCULATIONS.
  