Plan Review Notes
Plan Review Notes For Permit 14091024
Permit Number 14091024
Review Stop E
Sequence Number 2
Notes
Date Text
2014-12-11 09:33:5912/11/2014
 PROJECT: 307 PURITAN RD
 PERMIT#: 14091024
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED.
  
 1) FBC, WPB AMENDMENTS 107.2.1
 A. ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. THE ELECTRICAL
 PLANS, SHEET E1 ARE NOT SIGNED OR SEALED.
 FL SS 471, AND FL SS 668.001- 668.006
 B. ALL FINAL DRAWINGS, SPECIFICATIONS, PLANS, REPORTS,
 OR DOCUMENTS PREPARED OR ISSUED BY THE LICENSEE AND
 BEING FILED FOR PUBLIC RECORD AND ALL FINAL DOCUMENTS
 PROVIDED TO THE OWNER OR THE OWNER?S REPRESENTATIVE
 SHALL BE SIGNED BY THE LICENSEE, DATED, AND SEALED WITH
 SAID SEAL. THE ELECTRICAL PLANS, SHEET E1ARE NOT SIGNED
 OR SEALED.
  
 2) NEC 110.9
 VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS HAS A
 FAULT CURRENT RATING THAT IS SUFFICIENT AT NOMINAL
 CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED.
  
 3) NEC 210.23 (2) UTILIZATION EQUIPMENT FASTENED IN
 PLACE.
 THE TOTAL RATING OF UTILIZATION EQUIPMENT FASTENED IN
 PLACE, OTHER THAN LUMINAIRES, SHALL NOT EXCEED 50
 PERCENT OF THE BRANCHCIRCUIT AMPERE RATING. THE
 DISHWASHER AND DISPOSAL CAN NOT SHARE A CIRCUIT UNLESS
 PROOF AND BE SHOWN THAT NEITHER APPLIANCE WILL EXCEED
 50% OF THECRATED LOAD OF THE BRANCH CIRCUIT.
  
 4) NEC 210.52(E)(3)
 FOR A ONE FAMILY DWELLING AND EACH UNIT OF A TWO-FAMILY
 DWELLING THAT IS AT GRADE LEVEL, AT LEAST ONE
 RECEPTACLE OUTLET ACCESSIBLE WHILE STANDING AT GRADE
 LEVEL AND LOCATED NOT MORE THAN 2.0 M (61.2 FT) ABOVE
 GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE
 DWELLING. INDICATE THE REQUIRED GFI OUTLET AT TH THE
 FRONT OF THE RESIDENCE.
  
 5) NEC 210.12, 406.11
 ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED.
  
 6) NEC 210.8.
 ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES
 INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8)
 SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION
 FOR PERSONNEL. ALL OUTLETS IN THE GARAGE SHALL BE GFCI
 PROTECTED.
  
 7) NEC 408.4
 EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. PROVIDE THE REQUIRED OCPD IN THE PANEL
 FOR THE A/C CONDENSING UNIT. THE CIRCUIT CURRENTLY
 LISTED FOR THE A/C CU IS INDICATED ON THE FLOOR PLN AS
 THE DRYER CIRCUIT. INDIACTE THE REQUIERD OCPD FOR THE
 DRYER CIRCUIT AS WELL.
  
 8) NEC 220.16(2).
 LOADS FOR NEW CIRCUITS OR EXTENDED CIRCUITS IN
 PREVIOUSLY WIRED DWELLING UNITS SHALL BE CALCULATED IN
 ACCORDANCE WITH EITHER 220.12 OR 220.14, AS
 APPLICABLE.CORRECT THE LOAD CALCULATION TO INCLUDE THE
 REQUIRED 5KW LOAD FOR THE DRYER.
  
 9) NEC 210.63 SEE 210.8(A)(3),
 ONE 125VOLT, SINGLE-PHASE, 15 OR 20AMP GFI RECEPTACLE
 OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR
 THE SERVICING OF HEATING, AIR-CONDITIONING, AND
 REFRIGERATION EQUIPMENT. THE RECEPTACLE SHALL BE
 LOCATED ON THE SAME LEVEL AND WITHIN 25FT OF THE
 HEATING, AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT.
 THE RECEPTACLE OUTLET SHALL NOT BE CONNECTED TO THE
 LOAD SIDE OF THE EQUIPMENT DISCONNECTING MEANS.
  
 10) NEC 210.52 (A) GENERAL PROVISIONS. IN EVERY
 KITCHEN, FAMILY ROOM, DINING ROOM, LIVING ROOM, PARLOR,
 LIBRARY, DEN, SUNROOM, BEDROOM, RECREATION ROOM, OR
 SIMILAR ROOM OR AREA OF DWELLING UNITS, RECEPTACLE
 OUTLETS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 GENERAL PROVISIONS SPECIFIED IN 210.52(A)(1) THROUGH
 (A)(3). VERIFY SPACING THROUGHOUT.
  
 11) 210.70(A)(3)
 PROVIDE A LIGHTING OUTLET AND SWITCH FOR WHAT APPEARS
 TO BE A SECONDARY ATTIC ACCESS IN MASTER CLOSET.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  