Plan Review Notes
Plan Review Notes For Permit 14091024
Permit Number 14091024
Review Stop M
Sequence Number 1
Notes
Date Text
2014-10-07 09:42:08SHOW ON MECHANICAL PLAN A COMPLETE HVAC SCHEDULE
 DESIGNER MUST SIGN & DATE ALL MECHANICAL SHEETS
 SHOW ON PLAN THE DUCT INSUL "R" VALUE--------------FBC
 EC 403.2
 CLOTHES DRYER MAKE-UP AIR FMC 504.5
 PROTECT AIRHANDLER AND DUCT FROM DAMAGE FMC 303.4