Date |
Text |
2014-10-24 16:42:52 | 10/24/2014 |
| PROJECT: NEW SFR 307 PURITAN RD. |
| PERMIT#: 14091024 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) PROVIDE SMOKE AND C/O ALARMS IN ALL ROOMS REQUIRED |
| BY THE FBC 314, 315 PROVIDE THE REQUIRED SMOKE AND C/O |
| DETECTORS IN THE MASTER BEDROOM. |
| |
| 2) INDICATE A PANEL SCHEDULE INDICATING THE USE OF A |
| MAIN BREAKER AND IDENTICATION OF ALL CIRCUITS. EVERY |
| CIRCUIT SHALL BE LEGIBLY IDENTIFIED AS TO ITS CLEAR, |
| EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC 408.4 |
| |
| 3) ADDITIONAL OUTLETS SHALL BE INSTALLED WHERE REQUIRED |
| BY THE NEC 210.52 |
| |
| 4) AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN |
| SERVICE GROUND. NEC 250.94 |
| |
| 5) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| SHALL BE REQUIRED FOR GENERATOR, POOL, VACUUM, |
| SECURITY, CCTV |
| |
| 6) IDENTIFY OUTLET BOXES TO SUPPORT CEILING-SUSPENDED |
| (PADDLE) FANS THAT WEIGH MORE THAN 16 KG (35 LB), THE |
| REQUIRED MARKING SHALL INCLUDE THE MAXIMUM WEIGHT TO BE |
| SUPPORTED. NEC314.27(D) |
| |
| 7) AT LEAST ONE SWITCH CONTROLLED LIGHT SHALL BE |
| INSTALLED AT ALL ATTIC ACCESS WHERE THESE SPACES ARE |
| USED FOR STORAGE OR CONTAIN EQUIPMENT REQUIRING |
| SERVICING. NEC210.70(3) |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |