Plan Review Notes
Plan Review Notes For Permit 14091024
Permit Number 14091024
Review Stop B
Sequence Number 1
Notes
Date Text
2014-10-22 12:22:21NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- BRING PLANS TO PALM BEACH COUNTY BUILDING (2300 N.
 JOG RD.) TO VERIFY IF FEES ARE DUE. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
  
 2- PROVIDE SOIL TEST REPORT. SEC. R401.4 OF 2010
 FBC-RESIDENTIAL.
  
 3- PROVIDE DRAINAGE PLAN AS REQUIRED BY SEC. R401.3 OF
 2010 FBC-RESIDENTIAL.
  
 4- SHEET A1:
 A) MASTER BATHROOM: PROVIDE A LANDING ON THE EXTERIOR
 SIDE OF THE DOOR AS REQUIRED BY SEC. R311.3 OF 2010
 FBC-RESIDENTIAL.
 B) REVISE INSULATION R-VALUE SPECIFIED FOR WALL BETWEEN
 GARAGE AND INTERIOR OF HOUSE. COORDINATE WITH THE
 ENERGY CALCULATIONS. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
 C) CLARIFY SIZE OF GARAGE OVERHEAD DOOR. OPENING
 DIMENSION SHOWN ON FLOOR AND FOUNDATION PLANS IS 12'-0"
 BUT SIZE OF DOOR SPECIFIED ON FLOOR PLAN AND ELEVATION
 IS 10' W X 7' DOOR. REVISE AS REQUIRED TO MATCH. SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
  
 5- SHEET A2: PROVIDE COMPLETE WALL SECTION THRU THE TWO
 STORY DINING ROOM AREA. SEC. 107.3.5.3 CITY AMENDMENTS
 TO FBC.
  
 6- SHEET A3:
 A) DESIGN CRITERIA: REVISE BUILDING DEPARTMENT. CORRECT
 BUILDING DEPARTMENT IS CITY OF WEST PALM BEACH NOT PALM
 BEACH COUNTY. SEC. 107.2.1 CITY AMENDMENTS TOP FBC.
 SAME APPLIES TO SHEET A4 AND A5.
 B) DESIGN CRITERIA: REVISE THE BOTTOM CHORD LIVE LOAD.
 THERE IS STORAGE ABOVE GARAGE. SEE TABLE R301.5 OF 2010
 FBC-RESIDENTIAL AND REVISE AS REQUIRED. SAME APPLIES TO
 SHEET A4 AND A5.
 C) REVISE CHIMNEY FRAMING DETAIL TO MATCH ACTUAL SHAPE
 OF CHIMNEY SHOWN ON THE EXTERIOR ELEVATIONS. AND
 PROVIDE ALL DIMENSIONS. SEC. 107.2.1 CITY AMENDMENTS.
  
 7- WALL SECTIONS ON SHEET S1:
 A) REVISE SPECIFICATIONS FOR THE HIGH RIBBED METAL LATH
 ATTACHMENT. REVISE THE NAIL SIZE AND SPECIFY THE
 NAILING SPACING TO SHOW COMPLIANCE WITH ASTM C1063 AS
 REQUIRED BY SEC. R703.6 OF 2010 FBC-RESIDENTIAL. NAIL
 SIZE SPECIFIED DOESN'T COMPLY WITH ASTM C1063.
  
 B) REVISE NUMBER OF STUCCO LAYERS TO COMPLY WITH SEC.
 R702.2.2 OF 2010 FBC-RESIDENTIAL. LESS THAN 3 COATS IS
 NOT ALLOWED.
  
 C) SPECIFY FIREBLOCKING AS REQUIRED BY SEC. R302.11 OF
 2010 FBC-RESIDENTIAL.
  
 D) SPECIFY SIZE OF ATTIC VENTILATION AS REQUIRED BY
 SEC. R806 OF 2010 FBC-RESIDENTIAL.
  
 E) DESIGNER OF RECORD TO SPECIFY THE ROOF TILE
 ATTACHMENT AS REQUIRED BY SEC. 107.2.1.2 OF CITY
 AMENDMENTS TO FBC. ALSO, REVISE SPECIFICATIONS FOR THE
 CONCRETE TILE UNDERLAYMENT. 30# FELT ALONE IS NOT
 ADEQUATE UNDERLAYMENT FOR CONCRETE TILE. SEC. R905.3.3
 OF 2010 FBC-RESIDENTIAL.
  
 F) COORDINATE SPECIFIED ATTIC INSULATION WITH THE
 ENERGY CALCULATIONS. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 8- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $291,332. THE
 PERMIT FEE BALANCE IS $5104.60.
  
 9- SPECIFY CARBON MONOXIDE ALARMS IN PLANS AS REQUIRED
 BY SEC. R315 OF 2010 FBC-RESIDENTIAL.
  
 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) PRECAST LINTELS AS SPECIFIED ON PLANS.
 B) OVERHEAD GARAGE DOOR AS SPECIFIED ON PLANS.
 COORDINATE WITH ITEM #4(C) ABOVE.
 C) ROOF TILE FOAM IF SPECIFIED BY THE DESIGNER OF
 RECORD IN ITEM #7(E) ABOVE. SEE ROOF TILE NOA FOR
 LISTED FOAM.
 D) ENTRY DOOR AS SHOWN ON PLANS. DRAWINGS SUBMITED ARE
 MISSING THE FLORIDA PRODUCT APPROVAL COVER PAGE. NEED
 THIS TO VERIFY IF DOOR WAS APPROVED OR NOT. IF THERE IS
 NOT FLORIDA PRODUCT APPROVAL, THEN DOOR MANUFACTURER
 MAY SUBMITT COMPLETE ENGINEERING ANALYSIS FOR LOCAL
 PRODUCT APPROVAL REVIEW.
 E) SIMPSON STRUCTURAL CONNECTOR SPECIFIED ON PLANS AND
 DETAILS. REVISE FLORIDA PRODUCT APPROVAL SPECIFIED ON
 SHEET A3 FOR CONNECTOR #1. NEED PRODUCT APPROVAL FOR
 2010 FBC. FL474 IS NOT CURRENT. AND, PROVIDE PRODUCT
 APPROVAL COVER PAGE FOR ALL CONNECTORS SPECIFIED IN ALL
 STRUCTURAL DETAILS. OR SPECIFY CURRENT FLORIDA PRODUCT
 APPROVAL NUMBER NEXT TO EACH CONNECTOR SPECIFIED.
  
 11-DESIGN PROFESSIONAL OF RECORD TO REVIEW AND APPROVE
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 OF
 CITY AMENDMENTS.
  
 12- ENERGY CALCULATIONS:
 A) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. SEC.
 103.2.3.2 OF 2010 FBC-ENERGY CONSERVATION.
 B) ACCORDING TO PLANS SUBMITTED, THERE IS NOT ELECTRIC
 WATER HEATER. REVISE AS REQUIRED. SEC. 103.2.1.1.2 OF
 2010 FBC-ENERGY CONSERVATION.
 C) REVISE DOORS INFORMATION ON SHEET 3 OF 5. THERE ARE
 NOT WOOD WOOD DOORS. SEE PLANS AND PRODUCT APPROVALS
 SUBMITTED. SEC. 103.2.1.1.2 OF 2010 FBC-ENERGY
 CONSERVATION.
 D) REVISE ORIENTATION OF WALLS, DOORS AND WINDOWS TO
 MATCH ACTUAL ORIENTATION SHOWN ON THE SURVEY. SEC.
 103.2.1.1.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 13- PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE
 WINDOWS AND DOORS SHOWING COMPLIANCE WITH THE U-FACTOR
 AND SHGC FACTOR SPECIFIED IN THE ENERGY CALCULATIONS IN
 ITEM #7. REQUIRED BY SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE AND REPLACE ALL REVISED SHEETS.
  