Plan Review Notes
Plan Review Notes For Permit 14090987
Permit Number 14090987
Review Stop E
Sequence Number 1
Notes
Date Text
2014-10-03 18:56:10PLAN REVIEW COMMENTS
  
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 ELECTRICAL
  
 1) ON SHEET P-2 UNDER EQUIPMENT SELECTION IS LISTED "
 HEATER (ELECTRIC): JANDY 400 BTU GAS " . PLEASE CLARIFY
 IF THE POOL HEATER WILL BE GAS OR ELECTRIC AND CORRECT
 THE NOTE ACCORDINGLY. FBC 107.2.1
  
 2) IF THE POOL HEATER IS ELECTRIC, SUBMIT LOAD
 CALCULATIONS TO SHOW THAT THE EXISTING SERVICE WILL
 ACCOMMODATE THE NEW HEAT PUMP. NEC 220.40
  
 3) IF THE POOL HEATER IS ELECTRIC, SUBMIT THE CUT
 SHEETS WITH THE ELECTRIC REQUIREMENTS FOR THE POOL
 HEATER. NEC 680.9
  
  
  