2014-10-07 08:12:02 | 10/7/2014 |
| PROJECT: SA/PD ADMINISTRATION |
| PERMIT#: 14090975 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| ELECTRICAL PLAN REVIEW |
| ACTION: |
| |
| 1) EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED |
| MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND |
| ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE |
| REQUIRED ILLUMINATION. EMERGENCY LIGHTING SYSTEMS SHALL |
| BE DESIGNED AND INSTALLED SO THAT THE FAILURE OF ANY |
| INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF |
| A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT |
| REQUIRES EMERGENCY ILLUMINATION. NEC 700.16. THERE IS |
| NOT ADAQUATE EMERGENCY ILLUMINATION AS DIRECTED BY THE |
| NEC 700.16 |
| |
| 2) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL |
| BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL |
| LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL |
| SWITCHES. THE BRANCH CIRCUIT THAT FEEDS UNIT EQUIPMENT |
| SHALL BE CLEARLY IDENTIFIED AT THE DISTRIBUTION PANEL. |
| EMERGENCY LUMINAIRES THAT OBTAIN POWER FROM A UNIT |
| EQUIPMENT AND ARE NOT PART OF THE UNIT EQUIPMENT SHALL |
| BE WIRED TO THE UNIT EQUIPMENT AS REQUIRED BY 700.9 AND |
| BY ONE OF THE WIRING METHODS OF CHAPTER 3. NEC |
| 700.12(F) |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |