Plan Review Notes For Permit 14090973 |
Permit Number |
14090973 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-10-03 16:09:40 | REVISION DENIED | | | | 1) THE TWO SETS OF ENERGY CALCULATIONS THAT WERE | | SUBMITTED WERE NOT REQUESTED NOR REQUIRED. PLEASE | | REVIEW THE (4) ITEMS THAT WERE REQUESTED ON THE | | CONDITIONALLY APPROVED HVAC PLANS (SHEET H-1). THEY ARE | | LISTED BELOW. IF YOU HAVE ANY QUESTIONS PLEASE CALL. | | WHEN SUBMITTING THE REQUESTED INFORMATION, PLEASE | | SUBMIT ALL OF THE REQUESTED INFORMATION AT THE SAME | | TIME UNDER THIS REVISION NUMBER. THIS WAY IT WILL COST | | LESS AND BE LESS CONFUSING THAN SUBMITTING THE ITEMS | | SEPARATELY. | | | | ITEMS PREVIOUSLY REQUESTED | | | | 1) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS FOR | | THE THE NEW A/C UNITS AS REQUIRED BY FBCR M1401.3. | | 2) SUBMIT AHRI CERTIFICATIONS FOR THE NEW HEATING AND | | COOLING EQUIPMENT. FBC ENERGY CONSERVATION SECTION | | 402.1.2.4. | | 3) REVISE THE SIZE OF THE THROUGH THE WALL TRANSFER | | GRILL AT THE GUEST BEDROOM TO COMPLY WITH FBCR M1602.4 | | FOR BALANCED RETURN AIR. | | TRANSFER GRILLS SHALL USE 50 SQUARE INCHES OF GRILL | | AREA TO 100 CFMS OF SUPPLY AIR. | | 4) PROVIDE TWO SETS OF AN EQUIPMENT ANCHORING DETAIL | | FOR THE MECHANICAL EQUIPMENT THAT IS EXPOSED TO WIND | | LOADS. FBCR M1307.2.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|