Plan Review Notes For Permit 14090907 |
Permit Number |
14090907 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-10-03 11:07:18 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | BUILDING | | | | 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE | | 9N-3. SPECIFICALLY, PROVIDE STATE OF FLORIDA OR | | MIAMI-DADE PRODUCT APPROVAL SUBMITTALS WITH FL# OR NOA | | #. | | | | 2) FBC 107.2.1 & 107.2.1.3 - SUBMIT TWO COPIES OF A | | STORM PANEL INSTALLATION SCHEDULE THAT CORRESPONDS WITH | | THE KEY PLAN THAT WAS SUBMITTED. SPECIFY THE STORM | | PANEL TYPE (STEEL OR POLYCARB), THE STRUCTURE TYPE, THE | | OPENING SIZE, THE WIND PRESSURE, THE ANCHOR, THE | | SHUTTER SPAN, ETC. I HAVE INCLUDED A LINK TO THE SITE | | THAT HAS MANY OF THE DEPARTMENTS FORMS INCLUDING THE | | SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE | | DEVICES. | | HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/ | | | | 3) SHOW THAT THE EGRESS DOOR REQUIRED BY FBC - R311.1 | | WILL REMAIN IN COMPLIANCE WITH FBC- R311.2 AND BE | | READILY OPENABLE FROM INSIDE THE DWELLING WITHOUT THE | | USE OF A SPECIAL KEY OR SPECIAL KNOWLEDGE OR EFFORT | | WHEN THE STORM PANELS ARE IN PLACE. |
|