Plan Review Notes For Permit 14090897 |
Permit Number |
14090897 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-09-30 16:47:06 | RESIDENTIAL (R2) FLOORING, BUILDING REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- COPIES OF IMPACT SOUND TRANSMISSION TEST (ASTM E | | 492) AND SOUND TRANSMISSION LOSS TEST (ASTM E 90) SHOW | | THAT THE TESTS WERE DONE FOR AN 8" CONCRETE SLAB WITH A | | SUSPENDED CEILING SYSTEM". IF THE PROPOSED INSTALLATION | | DOESN'T MATCH THIS TYPE OF FLOOR/CEILING ASSEMBLY, THEN | | THIS TEST CAN'T BE USED TO SHOW COMPLIANCE WITH THE | | SOUND TRANSMISSION REQUIREMENT OF SEC. 1207 OF 2010 | | FBC. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|