2014-10-01 13:37:08BACK TO R15
  
  
2014-10-01 13:33:0810/1/2014
 PROJECT: POWDER RM
 PERMIT#: 14090896
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 ELECTRICAL PLAN REVIEW
 ACTION:
  
 1) PROVIDE A SITE PLAN OR FLOOR PLAN TO INDICATE THE
 LOCATION OF THE NEW POWDER ROOM. IS IT INSIDE THE
 EXISTING CONDITIONED SPACE UNDER ROOF? OR IS THERE AN
 ADDITION BEING BUILT TO ADD THE NEW SPACE?
  
 1) PROVIDE ELECTRICAL PLANS TO INDICATE THE FOLLOWING:
 A. NEC 210.52(C)(3) BATHROOM BRANCH CIRCUITS. IN
 ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY
 OTHER PARTS OF THIS SECTION, AT LEAST ONE 20-AMPERE
 BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM
 RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER
 OUTLETS.
 B. 210.70 LIGHTING OUTLETS REQUIRED. LIGHTING OUTLETS
 SHALL BE INSTALLED WHERE SPECIFIED IN 210.70(A), (B),
 AND (C).
 (A) DWELLING UNITS. IN DWELLING UNITS, LIGHTING OUTLETS
 SHALL BE INSTALLED IN ACCORDANCE WITH 210.70(A)(1),
 (A)(2), AND (A)(3).
 (1) HABITABLE ROOMS. AT LEAST ONE WALL
 SWITCH?CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED IN
 EVERY HABITABLE ROOM AND BATHROOM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  