 PROJECT: LIFE IN PALM BEACH "SIGN "
 PERMIT#:
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) 600.3 LISTING.
 ELECTRIC SIGNS, SECTION SIGNS, AND OUTLINE LIGHTING ?
 FIXED, MOBILE, OR PORTABLE ? SHALL BE LISTED AND
 INSTALLED IN CONFORMANCE WITH THAT LISTING, UNLESS
 OTHERWISE APPROVED BY SPECIAL PERMISSION. INDICATE THE
 REQUIRED LISTING AND LABELING PER NEC 600.3 AND NEC
 110.3(B)
  
 2) NEC 600.5
 EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS
 SHALL BE PROVIDED WITH AT LEAST ONE OUTLET SUPPLIED BY
 A BRANCH CIRCUIT RATED AT LEAST 20 AMPERES THAT
 SUPPLIES NO OTHER LOAD. INDICATE THE REQUIRED SIGN
 CIRCUIT IS EITHER EXISTING TO REMAIN OR PROPOSED TO BE
 INSTALLED UNDER THIS SCOPE. IF IT IS TO BE INSTALLED
 UNDER THIS SCOPE A SEPARATE PERMIT BY A QUALIFIED
 ELECTRICAL CONTRACTO IS REQUIRED.
  
 3) NEC 600.6(A)(1) LOCATION.
 DISCONNECTS. EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR
 FEEDER CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR
 OUT-LINE LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN
 EXTERNALLY OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL
 OPEN ALL UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN
 OR OUTLINE LIGHTING SYSTEM THAT IT CONTROLS. INDICATE
 THE REQUIRED DISCONNECT WITHIN SIGHT OF THE SIGN.
  
 4) FBC-E 505.2.4
 ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL
 HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN
 NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME
 CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES
 SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS
 OF POWER FOR A MINIMUM OF 10 HOURS. THE DEDICATED SIGN
 CIRCUIT SHALL COMPLY WITH THE PROVISIONS OF THE FBC-E
 505.2.4.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,