Plan Review Notes For Permit 14090840 |
Permit Number |
14090840 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-10-06 10:49:27 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | SHEET A 3.01, DOOR 07 SHALL NOT SWING INTO THE HALLWAY | | MORE THAN 1/2 OF THE HALLWAY WIDTH OR IT SHALL NOT BE | | INSTALLED TO SWING INTO HALLWAY. | | | | THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE | | FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND | | COMPLIANCE. | | | | THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE | | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE | | CONSTRUCTION PERIOD. | | | | ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER | | SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND | | BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, | | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE | | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL | | AND COMPLETE PROTECTION IS RETURNED. | | | | | | |
|