Plan Review Notes For Permit 14090840 |
Permit Number |
14090840 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-09-24 12:50:24 | DATE: 9/24/2014 | | PROJECT: NORTHPOINT SUITE 340 | | PERMIT#: 14090840 | | CODE: 2008 EDITION OF THE NEC | | 2010 EDITION OF THE FBC | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | 1ST ELECTRICAL PLAN REVIEW | | ACTION: PROVISO | | | | 1) FBC-ENERGY | | 505.2 LIGHTING CONTROLS (MANDATORY). | | LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS | | REQUIRED IN SECTIONS 505.2.1, 505.2.2, 505.2.3 AND | | 505.2.4. | | 505.2.2 AUTOMATIC LIGHTING SHUTOFF. | | BUILDINGS LARGER THAN 5,000 SQUARE FEET (465 M2) SHALL | | BE EQUIPPED WITH AN AUTOMATIC CONTROL DEVICE TO SHUT | | OFF LIGHTING IN THOSE AREAS. | | REVISE PLANS AND INSTALLATION IN COMPLIANCE WITH | | SECTION 505 AS DESRIBED ABOVE. | | | | 2) VERIFY DEDICATED SPACE AND WORKING CLEARANCE IN THE | | ELECTRICAL ROOM WHEN INSTALLING THE NEW PANEL RL AS | | REQUIRED BY THE NEC 110.26 | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|