Plan Review Notes For Permit 14090826 |
Permit Number |
14090826 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-10-11 12:27:54 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | FBC 2010 RESIDENTIAL 301 | | | | 1. SUBSTRATE IS NOT CLEAR. "CONCRETE BLOCK" IS | | SPECIFIED FOR OPENINGS 1-5. FOR VERTICAL INSTALLATIONS, | | IS THIS CONCRETE BLOCK (MASONRY) TOP AND BOTTOM, OR | | CONCRETE TOP, BLOCK BOTTOM (TYPICAL OF CBS STRUCTURES)? | | | | FOR HORIZONTAL INSTALLATION #1, FILLED CELLS ON EACH | | SIDE WOULD REQUIRE USE OF THE "MASONRY" ANCHOR SPACING. | | FOR THE CONNECTION TYPES SELECTED, SUBSTRATE MUST BE | | CONCRETE. | | | | CONNECTION TYPES 1 AND 6 REQUIRE A CONCRETE SUBSTRATE | | (SEE ANCHOR CHART, MASONRY COLUMN STATES "NA" FOR | | SPACING). | | | | CONNECTION TYPE 2 ALLOWS A MASONRY SUBSTRATE, BUT 7" IS | | REQUIRED, 9" PROPOSED. | | | | PLEASE CLARIFY SUBSTRATE, REVISE ANCHOR SPACING AND | | CONNECTION TYPE AS APPLICABLE. | | | | 2. REVISE FLOOR PLAN TO PROVIDE ROOM DESIGNATIONS FOR | | OPENINGS/DOORS MARKED EGRESS FBC R 310.4. | | |
|