Plan Review Notes
Plan Review Notes For Permit 14090826
Permit Number 14090826
Review Stop B
Sequence Number 2
Notes
Date Text
2014-10-11 12:27:54****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
  
 FBC 2010 RESIDENTIAL 301
  
 1. SUBSTRATE IS NOT CLEAR. "CONCRETE BLOCK" IS
 SPECIFIED FOR OPENINGS 1-5. FOR VERTICAL INSTALLATIONS,
 IS THIS CONCRETE BLOCK (MASONRY) TOP AND BOTTOM, OR
 CONCRETE TOP, BLOCK BOTTOM (TYPICAL OF CBS STRUCTURES)?
  
 FOR HORIZONTAL INSTALLATION #1, FILLED CELLS ON EACH
 SIDE WOULD REQUIRE USE OF THE "MASONRY" ANCHOR SPACING.
 FOR THE CONNECTION TYPES SELECTED, SUBSTRATE MUST BE
 CONCRETE.
  
 CONNECTION TYPES 1 AND 6 REQUIRE A CONCRETE SUBSTRATE
 (SEE ANCHOR CHART, MASONRY COLUMN STATES "NA" FOR
 SPACING).
  
 CONNECTION TYPE 2 ALLOWS A MASONRY SUBSTRATE, BUT 7" IS
 REQUIRED, 9" PROPOSED.
  
 PLEASE CLARIFY SUBSTRATE, REVISE ANCHOR SPACING AND
 CONNECTION TYPE AS APPLICABLE.
  
 2. REVISE FLOOR PLAN TO PROVIDE ROOM DESIGNATIONS FOR
 OPENINGS/DOORS MARKED EGRESS FBC R 310.4.
  