Plan Review Notes For Permit 14090826 |
Permit Number |
14090826 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-09-30 10:04:40 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. FBC 2010 RESIDENTIAL 301, PROVIDE CALCULAITNS FOR | | DESIGN PRESSURES, OR PROVIDE SIGNED AND SEALED | | ENGINEERING, OR USE THE PRESSURES IN TABLE R301.2(2) AS | | ADJUSTED BY 301.2(3). SEE OPENING 3. -39 PSF IS | | PROPOSED, BUT FOR EXPOSURE C, 25' MRH, 10 SF A DESIGN | | PRESSURE OF -45.8 IS REQUIRED. | | | | 2. THE COLUMN "SHUTTER MOUNTING CONNECTION TYPE PER | | PRODUCT APPROVAL" IS BLANK. PLEASE COMPLETE SO PROPOSED | | ANCHORING FOR EACH OPENING CAN BE REVIEWED. | | | | |
|