2014-09-30 10:04:40****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
  
 1. FBC 2010 RESIDENTIAL 301, PROVIDE CALCULAITNS FOR
 DESIGN PRESSURES, OR PROVIDE SIGNED AND SEALED
 ENGINEERING, OR USE THE PRESSURES IN TABLE R301.2(2) AS
 ADJUSTED BY 301.2(3). SEE OPENING 3. -39 PSF IS
 PROPOSED, BUT FOR EXPOSURE C, 25' MRH, 10 SF A DESIGN
 PRESSURE OF -45.8 IS REQUIRED.
  
 2. THE COLUMN "SHUTTER MOUNTING CONNECTION TYPE PER
 PRODUCT APPROVAL" IS BLANK. PLEASE COMPLETE SO PROPOSED
 ANCHORING FOR EACH OPENING CAN BE REVIEWED.
  
  