Plan Review Notes For Permit 14090822 |
Permit Number |
14090822 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-09-25 16:15:19 | THIS PERMIT WAS REVIEWED AND FAILED BY ROY LINDOW WITH | | THE FOLLOWING COMMENTS. | | | | PERMIT APPLICATION #14090822. | | | | PROVIDE FIRE SPRINKLER PROTECTION FOR INTERIOR OF | | TEMPORARY STRUCTURE. | | | | PROVIDE VISIBLE AND AUDIBLE NOTIFICATION APPLIANCES FOR | | INTERIOR OF STRUCTURE. | | | | PROVIDE EMERGENCY LIGHTING FOR INTERIOR OF TEMPORARY | | STRUCTURE. | | | | ADDITIONAL EXIT SIGNAGE TO BE COORDINATED WITH THE | | PREVENTION BUREAU. | | | | PROVIDE FREE EGRESS FROM BACK OF SUBWAY AND | | MULTI-PURPOSE ROOM BOTH EXITS ARE OBSTRUCTED BY PIPE | | AND DRAPE. | | | | PROVIDE FLAME SPREAD AND SMOKE DEVELOPMENT RATING FOR | | RED TEMPORARY WALLS SHOWN ON DRAWING. | | | | FLAME SPREAD AND SMOKE DEVELOPMENT DO NOT MEET MINIMUM | | REQUIREMENTS OF NFPA 101. | | |
|