2014-09-26 14:22:18 | BUILDING PLAN REVIEW |
| PERMIT: 14090822 |
| ADD: 4801 DREHER TRAIL NORTH |
| CONT: HEDRICK BROTHERS/ GRISSELL SANTANA |
| TEL: (561)315-4380 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: FRI. SEPT. 26/ 2014 |
| ACTION: DENIED |
| |
| 1) THE SUBMITTED PLANS DOES NOT CLEARLY INDICATE HOW |
| THE TEMPARARY WALLS ARE TO PLACED IN SECURE LOCATIONS |
| TO PREVENT THEM FROM BEING TIPPED. HEIGHT AND WIDTH OF |
| WALLS OR PANELS HAS NOT BEEN PROVIDED. SEE TABLE 1604.3 |
| FOOTNOTE "B". INTERIOR PARTITIONS NOT EXCEEDING 6 FEET |
| IN HEIGHT AND FLEXIBLE, FOLDING AND PORTABLE PARTITIONS |
| ARE NOT GOVERNED BY THE PROVISIONS OF THIS SECTION. THE |
| DEFLECTION CRITERION FOR INTERIOR PARTITIONS IS BASED |
| ON THE HORIZONTAL LOAD DEFINED IN SECTION 1607.13. |
| 1607.13 INTERIOR WALLS AND PARTITIONS. |
| INTERIOR WALLS AND PARTITIONS THAT EXCEED 6 FEET (1829 |
| MM) IN HEIGHT, INCLUDING THEIR FINISH MATERIALS, SHALL |
| HAVE ADEQUATE STRENGTH TO RESIST THE LOADS TO WHICH |
| THEY ARE SUBJECTED BUT NOT LESS THAN A HORIZONTAL LOAD |
| OF 5 PSF (0.240 KN/M2). |
| EXCEPTION: FABRIC PARTITIONS COMPLYING WITH SECTION |
| 1607.13.1 SHALL NOT BE REQUIRED TO RESIST THE MINIMUM |
| HORIZONTAL LOAD OF 5 PSF (0.24 KN/M2). |
| |
| 2) FINISHES: PLEASE REVIEW 2010 FBC-B TABLE 803.9 |
| INTERIOR WALL FINISHES FOR A3 OCCUPANCY/ SPRINKLERED, |
| "C" FINISH . FLAME SPREAD OF 76-200 SMOKE DEVELOPMENT |
| OF 0-450. FABRI TEST FAILED FLAME SPREAD OF 310/ SMOKE |
| DEVELOPMENT OF 690. |
| 03.5 TEXTILE WALL COVERINGS. |
| WHERE USED AS INTERIOR WALL FINISH MATERIALS, TEXTILE |
| WALL COVERINGS, INCLUDING MATERIALS HAVING WOVEN OR |
| NONWOVEN, NAPPED, TUFTED, LOOPED OR SIMILAR SURFACE AND |
| CARPET AND SIMILAR TEXTILE MATERIALS, SHALL BE TESTED |
| IN THE MANNER INTENDED FOR USE, USING THE PRODUCT |
| MOUNTING SYSTEM, INCLUDING ADHESIVE, AND SHALL COMPLY |
| WITH THE REQUIREMENTS OF SECTION 803.1.2, 803.1.3 OR |
| 803.1.4. |
| |
| 803.6 TEXTILE CEILING COVERINGS. |
| WHERE USED AS INTERIOR CEILING FINISH MATERIALS, |
| TEXTILE CEILING COVERINGS, INCLUDING MATERIALS HAVING |
| WOVEN OR NONWOVEN, NAPPED, TUFTED, LOOPED OR SIMILAR |
| SURFACE AND CARPET AND SIMILAR TEXTILE MATERIALS, SHALL |
| BE TESTED IN THE MANNER INTENDED FOR USE, USING THE |
| PRODUCT MOUNTING SYSTEM, INCLUDING ADHESIVE, AND SHALL |
| COMPLY WITH THE REQUIREMENTS OF SECTION 803.1.2 OR |
| 803.1.4. |
| |
| 3) THE PLANS DO NOT PROVIDE WHERE THE EXIT AND |
| DIRECTIONAL SIGNS WILL BE LOCATED. 2010 FBC-B 1006.3.1 |
| & 1006.3.8. |
| |
| 4) FBC-B 1008.1 MEANS OF EGRESS DOORS SHALL BE READILY |
| DISTINGUISHABLE FROM THE ADJACENT CONSTRUCTION AND |
| FINISHES SUCH THAT THE DOORS ARE EASILY RECOGNIZABLE AS |
| DOORS. MIRRORS OR SIMILAR REFLECTING MATERIALS SHALL |
| NOT BE USED ON MEANS OF EGRESS DOORS. MEANS OF EGRESS |
| DOORS SHALL NOT BE CONCEALED BY CURTAINS, DRAPES, |
| DECORATIONS OR SIMILAR MATERIALS. |
| |
| IT WOULD APPEAR THE OCCUPANCY CLASSIFICATION MAY NEED |
| TO BE CHANGED OR VIEWED AS ASPECIAL AMUSEMENT BUILDING |
| SEE SECTION 411. A SPECIAL AMUSEMENT BUILDING IS ANY |
| TEMPORARY OR PERMANENT BUILDING OR PORTION THEREOF THAT |
| IS OCCUPIED FOR AMUSEMENT, ENTERTAINMENT OR EDUCATIONAL |
| PURPOSES AND THAT CONTAINS A DEVICE OR SYSTEM THAT |
| CONVEYS PASSENGERS OR PROVIDES A WALKWAY ALONG, AROUND |
| OR OVER A COURSE IN ANY DIRECTION SO ARRANGED THAT THE |
| MEANS OF EGRESS PATH IS NOT READILY APPARENT DUE TO |
| VISUAL OR AUDIO DISTRACTIONS OR IS INTENTIONALLY |
| CONFOUNDED OR IS NOT READILY AVAILABLE BECAUSE OF THE |
| NATURE OF THE ATTRACTION OR MODE OF CONVEYANCE THROUGH |
| THE BUILDING OR STRUCTURE. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |