2014-09-27 07:45:181) SECTION 616.1 OF THE 2010 FUEL GAS CODE MANDATES
 THAT THE GENERATOR SHALL BE INSTALLED IN ACCORDANCE
 WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS AND
 NFPA 37. NFPA 37 REQUIRES THE GENERATOR TO BE A MIN. OF
 5 FT. FROM OPENINGS IN WALLS AND 5 FT. FROM STRUCTURES
 HAVING COMBUSTIBLE WALLS UNLESS THE WALL IS FIRE RATED
 WITH A RATING OF AT LEAST ONE HOUR OR THE WEATHERPROOF
 ENCLOSURE IS CONSTRUCTED OF NONCOMBUSTIBLE MATERIALS,
 AND IT HAS BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE MATERIALS OUTSIDE
 THE ENCLOSURE. THE GENERATOR IS SHOWN 18 INCHES FROM
 THE BUILDING WALLS.
 2) SHOW THAT THE GENERATOR IS A MIN. 5 FT. AWAY FROM
 ALL BUILDING OPENINGS.
 3) SUBMIT 2 COPIES OF THE MANUF. INSTALLATION
 INSTRUCTIONS FOR THE GENERATOR.
  
  
 PLUMBING PLAN REVIEW